(1) IP 30/NEMA 1/UL Type 1 rating requires installation of the PowerFlex 520-Series IP 30/NEMA 1/UL Type 1 option kit, catalog number 25-JBAx.
(2) For catalogs 25B-D1P4N104 and 25B-E0P9N104, the temperature listed under the Max. (Derate) column is reduced by 5 °C (9 °F) for all mounting methods.
(3) For catalogs 25B-D1P4N104 and 25B-E0P9N104, the temperature listed under the Max. with Control Module Fan Kit (Derate) column is reduced by 10 °C (18 °F) for vertical and vertical with zero stacking
mounting methods only.
(4) Catalogs 25B-D1P4N104 and 25B-E0P9N104 cannot be mounted using either of the horizontal mounting methods.
(5) Requires installation of the PowerFlex 520-Series Control Module Fan Kit, catalog number 25-FANx-70C.
Current Derating Curves
Vertical Mounting
Single Drive
120
IP 30/NEMA 1
110
100
90
0
70
60
50
40
30
35
40
45
50
55
60 65 70 75 0
Ambient Temperature (°C)
Horizontal Mounting/Floor
Single Drive
120
110
100
90
0
70
60
50
40
30 35
40 45
50 55
60 65
Ambient Temperature (°C)
16
for option kits.
Ambient Temperature
(1)
Enclosure Rating
Minimum
IP 20/Open Type
IP 30/NEMA 1/UL Type 1
IP 20/Open Type
-20 °C (-4 °F)
IP 30/NEMA 1/UL Type 1
IP 20/Open Type
IP 20/Open Type
with Control
Module Fan Kit
IP 20/Open Type
with Control
Module Fan Kit
IP 20/Open Type
70 75 0