Connecting Power To Cisco Asr 1004 Router - Cisco ASR 1004 Overview And Installation

Hide thumbs Also See for ASR 1004:
Table of Contents

Advertisement

Connecting Power to Cisco ASR 1004 Router

Connecting Power to Cisco ASR 1004 Router
The covers are an integral part of the safety design of the product. Do not operate the unit without the
Warning
covers installed. Statement 1077
When you install the unit, the ground connection must always be made first and disconnected last. Statement
Warning
1046
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1003
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1030
This section provides the procedures for connecting AC-input and –48 VDC input power to your Cisco ASR
1004 Router.
The –48 VDC power supply for the Cisco ASR 1006, ASR 1004, and ASR 1002 routers operate at individual
specifications. The following table shows the common input ranges and circuit breaker requirements.
Table 2: Cisco ASR 1000 Series Router – 48 VDC Power Supply System Input Requirements
Cisco ASR 1000
Series Router
DC Power
Supply
Cisco ASR 1006
Cisco ASR 1004
Cisco ASR 1002
Cisco ASR 1000 Series Router Hardware Installation Guide
28
System Input
Circuit Breaker
Rating (Amps)
Amps
Minimum
40
Always 50
24
30
16
20
Cisco ASR 1004 Router Overview and Installation
AWG # Wire
Maximum
Minimum
Always AWG
#6 wire
40
10
30
12
Maximum
8
10

Advertisement

Table of Contents
loading