Download Print this page

Emerson 818-7235 Quick Start Manual page 4

Site supervisor 10 inch display

Advertisement

Direct Connect to Site Supervisor
If connecting directly to a Site Supervisor, the following Static IP Address configuration must be entered:
Address: 192.168.1.200 (the last three digits i.e., 200 may be any number between 2 - 249)
Netmask: 255.255.255.0
Gateway: Should be blank
Save Network Configuration
1. After all changes are made, tap Close on the Display keyboard and then tap SAVE (top center).
2. After changes are saved, a confirmation message will appear. Tap OK.
3. After saving the configuration on the System Settings menu, tap Exit and wait for the browser Settings menu to appear.
Step 3: Setting Up the Browser Startup Page
1. Tap Set pages (under Settings>On startup) and enter the IP Address for Site Supervisor and configure the first page of
the browser. The Startup pages window opens where you can enter the URL in the Enter URL field.
2. For DHCP or Static IP, enter the standard information: http://sitesupervisorIP in the Enter URL field, but if you are directly
connected to the Site Supervisor, the IP Address must be http://192.168.1.250. The firmware should already be
preloaded with this IP address.
3. Tap Enter and Close on the keyboard to see full screen. Tap OK to save.
4. Manually cycle power to the Display only (do not cycle power to the Site Supervisor).
5. The Display will boot up and the browser will open directly to the Site Supervisor home page.
Note that to go back to the browser login screen at any time, press and hold the top left portion of the Display.
In case of power failure or connectivity problems between the Display and Site Supervisor:
First, try to restore connectivity between the Display and Site Supervisor and verify the Site Supervisor is powered ON and the Ethernet
cable is properly connected between the Display and Site Supervisor.
A There is no Internet connection screen may appear and timeout after three attempts to load the Site Supervisor Homepage.
After this screen times out, a login screen will load. Do not log into this screen: instead, touch Load Homepage in the upper
right corner. The Site Supervisor Homepage login screen will load if the Site Supervisor is connected properly to the Display and
powered up.
Log into Site Supervisor on this Homepage:
Document Part # 026-4159 Rev 2
©2017 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com for the latest technical documentation and updates.
Touch Load Homepage
Log Into Site Supervisor Homepage