Page 2
Central Unit Ⓐ (pre-installed into a pliance. Install and check the application ac- cooker hood) Follow these instructions carefully and cording to the instructions. Safera • Power Supply Ⓓ is not liable for any damages or ex- pay particular attention to the instruc- •...
Page 3
45 - 75 cm 60 - 90 cm 60 - 75 cm Compatibility 1.2 Central Unit Ⓐ Safera Stove Guard is compatible with ❶ Child proof lock button Depth most electrical cookers, hobs and ovens ❷ OK button Align the Central Unit with the centre meant for household use: ❸...
Page 4
Service and replacement of the ex- tinguishing unit Ⓔ may only be done ѧ HINT by service authorized by Safera. With some of the cooker hood mod- els the extinguishing unit Ⓔ is prein- Make sure that the hose is not stalled in the factory: in that case en- squeezed after the installation.
Page 5
Installation - Step 2/6 Mount the Power Control Unit Ⓒ Install the Power Control Unit according to the following instructions. PCU6.3-F PCU6.1-P Fixed 3-phase connection. 1-phase, 3-pin plug OUT. See pages 10-11. See pages 16-17. PCU6.3-P PCU6.1-S Perilex-connectors. Schuko-connectors. See pages 12-13.
Page 6
PCU6.3-F - Installation Fixed 3-phase connection. 78 mm 60 mm 225,5 mm 42 mm Optional water sensor connection. See chapter MICRO DISCONNECTION ѥ WARNING ⚐ ATTENTION Make sure that there is no power sup- Install the power control unit Ⓒ so ply to the cooker and the oven by re- that it is not exposed to moisture.
Page 7
PCU6.3-P - Installation 3-phase, Perilex-connectors. Mount the power con- trol unit Ⓒ on the wall behind the cooker or into the cabinet next to the cooker. 225,5 mm 51 mm + Perilex MICRO DISCONNECTION ѥ WARNING ⚐ ATTENTION Make sure that there is no power sup- Install the power control unit Ⓒ...
Page 8
PCU6.1-F - Installation Fixed 1-phase connection. 78 mm 60 mm Optional water sensor connection. 225,5 mm See chapter 4. 42 mm 230 V MAX. 25 / 32 A * MICRO DISCONNECTION * Check specifications on the cover of the Power Control Unit. ѥ...
Page 9
PCU6.1-P - Installation 4xA A 1-phase, 3-pin plug. Optional water sensor connection. See chapter 4. 226 mm 40 mm 230 V MAX. 25 / 32 A * MICRO DISCONNECTION * Check specifications on the cover of the Power Control Unit. Connect the stove ѥ...
Page 10
PCU6.1-S - Installation 1-phase, Schuko-connectors. Mount the power control unit Ⓒ on the wall behind the cooker or into the cabinet next to the cooker. 225,5 mm L = 700 mm Optional water sensor 46,5 mm connection. + Schuko See chapter 230 V MAX.
Page 11
Installation - Step 3/6 Installation - Step 4/6 Set up the wireless connection Calibrate the system Connect the power supply Ⓓ to the Sensor unit Ⓐ: indicator light panels ❽ are When the indicator light panels ❽ start blinking yellow-green, you need to cali- lit in purple.
Page 12
Installation - Step 5/6 Adjust the alarm limit Check clos- When adjust Location of the Installation Alarm Limit Color of the indicator Number of Alarm Limit recommended the alarm limit, the Cooker Height (1-12) light panels ❽ beeps alarm limit from the new alarm limit is •••...
Page 13
Installation - Step 6/6 Check-list 3. Installation troubleshooting Check the working order of the appliance and fill in the installation checklist: Problem Remedy Installation is not You can re-start the installation process anytime by proceeding as expected. pressing the adjustment mode button ❼ for five seconds until you hear the signal and continue from step 3/6.
Page 14
4. Installing the Water Leakage Sensor (optional) Stove Guard can be equipped with max. four Safera Water Leakage Sensors. The sensors are placed in the typical leak- age areas, e.g. under the dishwasher or sink. Attach the sensors Ⓕ in place.