Frame Weights Calculation - ABB SafeGear Technical And Application Manual

5/15 kv, up to 50 ka arc-resistant switchgear
Table of Contents

Advertisement

S A F E G E A R ® 5/ 1 5 K V, U P TO 5 0 K A A R C - R E S I S TA N T S W I TC H G E A R
4 4

Frame weights calculation

All frame styles
To calculate the weight of a frame, identify the cur-
rent rating for each module. Select the weights
from the appropriate column in the adjoining table
for SafeGear components.
A frame consists of one bus and cable module and
the approriate circuit breaker and auxiliary mod-
ules. The weight of the circuit breaker is given sep-
arately and must be added.
Low voltage modules may contain significant
amount of secondary equipment and wiring. De-
pending on the extent of secondary protection and
control equipment, ABB recommends adding 20%
to 50% of the empty weight of the module.
Typical frame weights are listed in the adjoining ta-
ble. Weights include all modules and components
previously listed.
Basic frame
Circuit breaker
configuration
(rating)
One circuit
1200
breaker
2000
3000
4000
Two circuits
1200/1200
breakers
1200/2000
One circuit
1200
breaker, one VT
2000
3000
One circuit
1200
breaker, two VTs
2000
One circuit
1200
breaker, one VT
2000
One circuit
1200
breaker, one CPT
2000
fuse
Note: These weights do not include the circuit break-
ers. Please reference the AMVAC or ADVAC breaker
technical guides for more information
Weight
lbs
kg
2023
918
2441
1107
3331
1511
3461
1570
3013
1367
3302
1498
2440
1107
2858
1396
3748
1700
2859
1297
3277
1486
3210
1456
3628
1646
2590
1175
3008
1364

Hide quick links: