Available frame types

Two-high frames

Description
The two-high breaker frame consists of two 38-
inch breaker compartments with a 19-inch instru-
ment compartment in between for two breakers in
a single frame.
Cable termination information
Cable size
#2 AWG
#4 AWG
500 MCM
750 MCM
1000 MCM (2-hole)
1000 MCM (4-hole)
All ratings (refer to page 28 for floorplans)
# of terms
GCT option
single pad
per phase
4
BYZ-S
4
BYZ-S
4
BYZ-S
4
BYZ-L
2
BYZ-S
1
BYZ-S
Dimensions
Frame
Width (in)
2000/3000 A
36
breaker
All other frames
36
* Height includes plenum
Options
• Ground CTs
• Surge arrestors
- Distribution
- Intermediate
- Station
• Surge capacitor
• Ground studs
• Space heaters
• Cable supports
Height (in)*
Depth (in)
86.5 or 93.5
129.5
86.5 or 93.5
118