5.9. Connection Diagram

5.9.1. Power Terminal Designations
Incoming Power Source
Connect to L1, L2 & L3
terminals.
Phase sequence is not
important.
Protective Earth / Ground
connection.
The drive must be Earthed /
Grounded
5.9.2. Control Terminal Connections & Factory Settings
Open
+24V Supply (100mA) / External Input
Digital Input 1
Stop
Digital Input 2
Forward Rotation
Digital Input 3
Analog Speed Ref
Digital Inputs : 8 – 30 Volt DC
+ 10 Volt, 10mA Output
Analog Input 1
Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max
0 Volt Supply / External Input
Analog Input 2
Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max
SAFE TORQUE OFF Input
Also refer to page 24 for further information on the STO
Function.
Logic High = 18-30 Volt DC ("SAFE TORQUE OFF" Standby
mode)
Relay Contacts (Terminals 14-18)
250VAC / 30VDC
5A Maximum
L1
L2
L3
Closed
Run (Enable)
Reverse Rotation
Preset Speed
1
+24V
2
DI1
3
DI2
4
DI3
5
+10V
6
DI/AI4
7
0V
0V
8
AO1
9
0V
0V
10
DI/AI5
11
AO2
12
STO+
13
STO-
14
R01COM
15
R01NO
16
R01NC
17
R02NO
18
R02COM
Motor Connections
Connect the motor to the U, V & W
terminals.
The motor earth must be connected
to the drive
Optional Brake Resistor & DC Bus
Connections
Where a Brake resistor is used, it
"BR"
must be connected to the
"+"
terminals.
The
brake
resistor
should
be
protected
from
overheating by means of a
thermal switch which interrupts
the mains supply in a brake
resistor fault situation.
Output Speed
Output Current
Default Function :
Drive Ready
/ Fault
Default Function :
Running
23
and