9.3. Read Only Status parameters

9.3.1. Read Only Status parameter access and navigation.
The user must be in the Long Parameter group to gain access to the Read only status parameters. See section 9.1.1 for how to navigate to the
long parameter group.
In the Long Parameter Group when the user scrolls to parameter "0000", pressing
required Read only status parameter (as listed in the table above). Pressing
only status parameter.
For those parameters which have multiple values (e.g. software ID parameter 3301), pressing the
values within that parameter.
Pressing
returns to the next level up. If
(main parameter level, i.e. Parameter "0000").
The following table includes the descriptions of all Read Only status parameters.
Actual signals
No.
Name/Value
01 OPERATING DATA
0102
ROTOR SPEED (ESTIMATED)
0105
OUTPUT TORQUE
0107
DC BUS VOLTAGE
0109
APPLIED MOTOR VOLTAGE
0110
DRIVE TEMPERATURE
0111
PRE RAMP SPEED CONTROLLER
REFERENCE
0112
TORQUE CONTROLLER
REFERENCE
0113
DIGITAL SPEED REFERENCE
(MOTORISED POT)
0115
ENERGY CONSUMPTION kWh
METER
0120
ANALOG INPUT 1 APPLIED
SIGNAL LEVEL
0121
ANALOG INPUT 2 APPLIED
SIGNAL LEVEL
0126
PI CONTROLLER OUTPUT
0128
PI REFERENCE (SETPOINT)
0130
PI FEEDBACK LEVEL
0135
FIELDBUS COMMUNICATION
SPEED REFERENCE
0140
DRIVE LIFETIME OPERATING
TIME
0141
ENERGY CONSUMPTION MWh
METER
0160
DIGITAL INPUT STATUS
0181
MOTOR MAGNETISING
CURRENT (Id)
0182
MOTOR ROTOR CURRENT (Iq)
0183
DC BUS VOLTAGE RIPPLE LEVEL
0184
MOTOR STATOR RESISTANCE
(Rs)
0185
MOTOR STATOR INDUCTANCE
(Ls)
0186
MOTOR ROTOR RESISTANCE
(Rr)
0188
OPERATING TIME
ACCUMULATED WITH
HEATSINK TEMPERATURE
ABOVE 80°C
is then pressed again (without pressing
Description
Basic signals for monitoring the drive (read-only).
For selection of an actual signal to be displayed on the control panel, see parameter 3405 DISPLAY
SCALING SOURCE.
In Vector control mode, this parameter displays the estimated rotor speed of the motor.
Displays the instantaneous output torque level produced by the motor in %.
Displays the instantaneous DC Bus Voltage internally within the drive in V DC.
Displays the instantaneous output voltage from the drive to the motor V AC.
Displays the Instantaneous Heatsink Temperature measured by the drive in ˚C.
Displays the set point reference input applied to the drive internal speed controller in Hz.
Displays the set point reference input applied to the drive internal torque controller in %.
Displays the value of the drive internal Motorised Pot (used for keypad) speed reference in Hz.
Displays the amount of energy consumed by the drive in kWh. When the value reaches 1000, it is reset
back to 0.0, and the value of Parameter 0141 (*MWh meter) is increased.
Displays the signal level applied to analog input 1 (Terminal 6) in % after scaling and offsets have been
applied.
Displays the signal level applied to analog input 2 (Terminal 10) in % after scaling and offsets have been
applied.
Displays the output level of the PI controller in %.
Displays the setpoint input to the PI controller in %.
Displays the Feedback input signal to the PI controller in %.
Displays the setpoint being received by the drive from the currently active Fieldbus interface in Hz.
Displays the total operating time of the drive. The first value shown is the number of hours. Pressing
the Up key will display the minutes and seconds. (HH:MM:SS)
Displays the amount of energy consumed by the drive in MWh.
Displays the status of the drive inputs, starting with the left hand side digit = Digital Input 1 etc.
Displays the motor magnetising Current in AMPS providing an auto tune has been successfully
completed.
Displays the motor Rotor (torque producing) current in Amps, providing an auto tune has been
successfully completed.
Displays the level of ripple present on the DC Bus Voltage in V DC. This parameter is used by the
ACS255 for various internal protection and monitoring functions.
Displays the measured motor stator resistance in ohms, providing an auto tune has been successfully
completed.
Displays the measured motor stator inductance in H, providing an auto tune has been successfully
completed.
Displays the measured motor rotor resistance in ohms, providing an auto tune has been successfully
completed.
Displays the amount of time in hours and minutes that the ACS255 has operated for during its lifetime
with a heatsink temperature in excess of 80°C. This parameter is used by the ACS255 for various
internal protection and monitoring functions. (HH:MM:SS)
will display "0104", the User can then scroll to the
once more will then display the value of that particular Read
and
or
), the display changes to the next level up
keys will display the different