Booster Heater Variables for Controlling DHW Tank
• The FSV #3031 should be set to "1(On)" (Default) to use booster heater as an additional heat source for
DHW tank.
• Booster heater startup delay timer : In case of DHW request, this timer will delay the operation of
booster heater compared to heat pump.
– FSV #3032 (Default 20 min., Range 20 ~ 95 min.), In "Power" DHW mode, the delay timer will be
neglected, and the booster starts immediately.
– In "Economic" DHW mode, the DHW heating will be conducted only with heat pump.
– #3032 should be smaller than the maximum H/P time (#3025). If the delay time is set too high, it
might take very long time for DHW heating.
• Temperature difference determining the booster heater OFF temperature (T_BH OFF = Tu + #3033) :
FSV #3033, Default 0˚C, Range : 0 ~ 4˚C.
• Temperature difference determining the booster heater ON temperature (T_BH ON = T_BH OFF - 2)
NOTE
• The FSV #4022 for booster heater priority should be set to "0 (both)" (Default) or "2" (booster)
to use booster heater.
• If not(backup heater priority), the booster heater can be operated in case of no backup heater
demand.
#3033
T
BH OFF
OFF
T
BH ON
ON
T
U
T
HP MAX
MAX
#3022
T
HP OFF
OFF
#3023
T
HP ON
ON
HP
#3044
T
H
T
U
00.00
01.00
22.00
BH
HP
t
#3045
23.00
24.00
t
#3043
47
47