Field setting mode
Space Cooling
• Target water outlet temperature : U pper limit(#1011, Default 25˚C, Range : 18 ~ 25˚C),
– With this default FSV settings, user can change the target water outlet temperature within the
range of 5 ~ 25˚C for cooling.
• Target room temperature : U pper limit(#1021, Default 30˚C), Lower limit(#1022, Default 18˚C)
– With this default FSV settings, user can change the target room temperature within the range
of 18 ~ 30˚C for cooling.
Space Heating
• Target water outlet temperature : U pper limit(#1031, Default 55˚C, Range : 37 ~ 55˚C),
– With this default FSV settings, user can change the target water outlet temperature within the
range of 25 ~ 55˚C for heating.
• Target room temperature : U pper limit(#1041, Default 30˚C), Lower limit(#1042, Default 16˚C)
– With this default FSV settings, user can change the target room temperature within the range
of 16 ~ 30˚C for heating.
DHW Heating
• Target DHW tank temperature : U pper limit(#1051, Default 50˚C, Range : 50 ~ 70˚C),
– With this default FSV settings, user can change the target tank temperature within the range
of 40 ~ 50˚C for DHW heating.
NOTE
• The FSV #3011 in the wired remote controller should be set to "1 or 2" to use DHW function.
Water Law & Room Thermostat : Code 20∗∗
42
42
English
English
Lower limit(#1012, Default 16˚C, Range : 5 ~ 18˚C)
Lower limit(#1032, Default 25˚C, Range : 15 ~ 37˚C)
Lower limit(#1052, Default 40˚C, Range : 30 ~ 40˚C)
1
Ts
#2021/2031
#2022/2032
#2061/2071
#2062/2072
Heating WL
Floor FCU
#2011
#2012
Ts : Target Temp.
Cooling WL
Ta : Ambient Temp.
2
1
2
#2051
#2052
Ta