Annunciators F; Timer T - Mitsubishi MELSEC A1SCPU Handy Manual

Melsec a1s series
Table of Contents

Advertisement

I
PROGRAMMING
Bo
I
I
Link range of 1 st
station.
Link range of nth
B3FF
I
Usable as internal relays in each station
Link range not usable as internal relays
Usable
as
internal relays in each station
I
Annunciators F
I
Annunciators (F) are used for detecting faults or errors. By writing a fault detection
part of your sequence program using annunciators, with each individual fault being
represented by a corresponding annunciator being turned ON. The earliest
annunciator number detected is automatically written to the special data register
D9009. The annunciator numbers are then stored in special registers D9125 to
D9132 in the order in which they occur on a first in first out basis. The value of
special register D9124 is incremented by 1 each time any of the annunciators is
turned ON and decremented by 1 each time they are reset using the RST
instruction or the LED instruction is executed.
I
Timer T
I
The timers used in the A I S PLC are up-timing timers which begin timing when the
timer coil is switched ON, and times out when the present value reaches the set
value. The timer contacts then close when the timer times out.
There are three types of timer available, 100 ms timers which are set in time
divisions of
100
ms, 10 ms timers which are set in time divisions of 10 ms, and 100
ms retentive timers which are also set in time divisions of 100 ms. The retentive
retain their current present value when the coil of the timer is turned OFF before
timing out. With the other timers, the present value is reset to zero when this
happens. To clear the present value of retentive time use the RST instruction.
60