Outline Specifications
Maximum working head
Immersion heater rating (a.c. supply only)
Maximum primary circuit pressure
Rated pressure
Pressure drop across coils
Outer casing:
White textured plastic coated corrosion proofed steel
Water container:
Duplex stainless steel (grade 1.4362 to EN10088). 100% pressure tested to 15 bar.
Thermal insulation:
HCFC/CFC free (ODP Zero) fire retardant expanded polyurethane foam. Nominal thickness 50mm.
Immersion heater:
Alloy sheathed element and thermostat pocket in Duplex stainless steel plate.
Pipe connections:
All connections accept 22mm outside diameter pipe - compression nuts and olives supplied. Thread rate is 3/4" BSP
male parallel to accept standard 3/4" BSP female fittings if required. Secondary return tapping thread rate is 1/2" BSP
female parallel to accept standard 1/2"BSP male fittings if required (supplied plugged).
Safety features:
Manually resettable thermal cut-out on heating element thermostat.
Manually resettable thermal cut-out for primary heating. Must be wired in conjunction with a suitable motorised valve
located within the primary heating circuit (not supplied).
18
36005941_issue_07.indd 18
40 metres 0.4MPa (4 bar)
3kW @ 240V ~ 50Hz
2.8kW @ 230V ~ 50Hz
0.3MPa (3 bar)
0.2MPa (2.0 bar)
0.02MPa (0.2bar)