Frico SIRe AC Quick Manual page 23

Integrated room temperature sensor
Hide thumbs Also See for SIRe AC:
Table of Contents

Advertisement

GB
Fault on or missing,
mandatory Return water
sensor SIReWTA connected to
SIReB1/B2/B1EC.
Return water
E7
temp. sensor
error.
Wrong temperature is
displayed in SIReUA1.
E8
Internal
Fault on or missing internal
sensor Error
temperature sensor, SIReIT,
connected to SIReB1/B2/B1EC.
E10
Program error
Two or more SIReB1/B2/B1EC
(different
in the system have different
programs)
programs.
E12
Room
Fault on or missing external
sensor
room sensor, SIReRTX
error
connected to SIReA1X/C1X.
E14
Outdoor
Fault on or missing, mandatory
sensor
outdoor temperature sensor,
error
SIReOTX, connected to SIReA1X.
SIReA1X/C1X (external pc-board)
do not communicate.
Communication
E20
error
Cables are not original.
Room
Fault on internal room temperature
E21
sensor
sensor in SIReUA1.
error
E22
Multiple
Logging tool or an extra control
control
unit SIReUA1 is connected to the
units
system.
connected
E23
Firmware
Components of different releases
error
are used in the system.
30
SIRe Competent
Try to reset the alarm. Check connections and
cable. False errors can occur in conjunction
with communication error, check that all other
alarms have been reset. Measure resistance,
47kOhm at 25°C.
Confirm that WTA is connected to the SIReB1/
B2/B1EC and securely fastened to the return
water pipe and compare with what the actual
temperature is.
SIReRTX-sensor must not be connected to SIReB1/B2/
B1EC when the intention is to use return water sensor.
When SIReWTA is used, SIReRTX shall be connected to
the SIReA1X
Try to reset the alarm. Check connections and
cable. False errors can occur in conjunction with
communication error, check that all other alarms have
been reset. Measure resistance, 47kOhm at 25°C.
Try to reset the alarm. SIRe can control different types
of units, e.g. Fan heaters or air curtains, water or
electrical units, but they cannot be combined. The only
exception is ambient air curtains in combination with
either electrical or water heated units of the same model.
Check the datalabels of your units and contact Frico
technical support.
Try to reset the alarm. Check connections and
cable. False errors can occur in conjunction with
communication error, check that all other alarms have
been reset. Measure resistance, 47kOhm at 25°C.
Try to reset the alarm. Check connections and
cable. False errors can occur in conjunction with
communication error, check that all other alarms have
been reset. Measure resistance, 47kOhm at 25°C.
Try to reset the alarm. Check connections, modular
cables and terminals, between all units and components.
Systematically shift position of communication cables to
identify a broken terminal or cables.
Make sure communication cables are correct (Frico
original cables has a circuit diagram indicating how the
contacts shall be crimped on to the cable.)
Try to reset the alarm. Check connections and
cable. False errors can occur in conjunction with
communication error, check that all other alarms have
been reset. If the error is not rectified SIReUA1 must be
replaced.
Try to reset the alarm. The system will only support
one control unit, disconnect and reset alarm.
Make sure all units are from the same release, contact
Frico technical support.