Table - Alarm - Frico SIRe AC Quick Manual

Integrated room temperature sensor
Hide thumbs Also See for SIRe AC:
Table of Contents

Advertisement

GB

Table - Alarm

Error code
Cause
Motor alarm
A1
Unit only starts on high speed.
Over
A2
heating
alarm
Frost
A3
protection
alarm
Fixed run time before filter
alarm has been reached.
A4
Filter alarm
External
A5
alarm
28
SIRe Competent
Thermal contact has
deployed. One or more
motors are overheated.
Missing link on motor protection
on SIReB1/B2/B1EC.
Unit won't start.
The temperature in the unit
has exceeded the alarm limit
for overheating.
(Only units with internal
temperature sensor)
The temperature in the unit
has fallen below the alarm
limit for frost protection (only
water heated units with internal
temperature sensor and/
or return water temperature
sensor SIReWTA).
The external filter guard has been
activated.
External alarm input (terminal
9-10) on SIReA1X/SIReC1X has
been activated
Action
Check that nothing is obstructing the unit's air intake
and exhaust.
When the overheated motor has cooled the thermal
switch shuts again and the alarm can be reset. At
repeated alarms, check the motors, replace damaged
motors.
For units having built-in thermal protection but without
external connection, the motor protection terminals must
be linked.
For units having built-in thermal protection but
without external connection, the motor protection
terminals must be linked.
Check motor and transformer connection terminal on
the SIReB1/B2/B1EC-pc board.
Check that nothing is obstructing the unit's air intake
and exhaust.
Check function of the contactors (E), Check function
of actuator and valve, flow temperature and bypass
settings (W).
Check internal temperature sensor, measure
resistance, 47kOhm at 25°C.
Check the function of the actuator, valve and
bypass settings.
Check the temperature and flow of the hot water supply.
In event of an alarm there is a risk that the coil is
damaged, check carefully for leakage and replace
the water heating coil if damaged.
Replace or clean the filter, if neccessary adjust the fixed
time based on how dirty the filter was and reset the alarm.
Replace or clean the filter, if neccessary adjust settings
of the filter guard based on how dirty the filter was and
reset the alarm.
Check the external alarm.