Wait Segments; Program Cycling; Creating A Program - Carbolite Gero 3508 Installation, Operation And Maintenance Instructions

1100 'c ashing furnace aaf model 18 litres
Table of Contents

Advertisement

3.8.3

Wait Segments

Wait prevents the program proceeding to the next segment, in a similar way to
holdback, until the selected 'Wait-For' parameter has been met. There are 5 'Wait For'
parameters. The first 4 only work if there are configured inputs to the controller.
1. PrgIn1 Wait until Input 1 is true
2. PrgIn2 Wait until Input 2 is true
3. PrgIn 1&2 Wait until Inputs 1 AND 2 are true
4. PrgIn 1or2 Wait until Inputs 1 OR 2 is true
5. PVWaitIP Wait until the measured temperature reaches a threshold value before
continuing. It can operate in one of 4 ways:
1. 'Abs Hi' Wait until the measured temperature is greater than or equal to a
value 'WaitVal' set for that segment.
2. 'Abs Lo' Wait until the measured temperature is less than or equal to a value
'WaitVal' set for that segment.
3. 'Dev Hi' Wait until the measured temperature exceeds a fixed* threshold by
an amount 'WaitVal' set for that segment.
4. 'Dev Lo' Wait until the measured temperature drops below a fixed* threshold
by an amount 'WaitVal' set for that segment.
* The fixed threshold used by deviation parameters is set in the configuration level of
the programmer and if required should be requested when purchasing a product from
Carbolite Gero.
3.8.4

Program Cycling

The 'Cycles' parameter sets the number of times the program will operate.
The default setting is 1 cycle.
To change the number of cycles, press page
display shows 'Prog Cycles', then press up
Or press down
to set cycling to continuous.
3.8.5

Creating a Program

From the home display, press page
the display will show "ProgEdit
Program number
On P10 or P25 models press up
display will show that new programs have only one segment.
Holdback Value
Press scroll
until the display shows 'Holdback Value". If required: Press up
down
to set a value. This value will be used in any segment where a 'Holdback Type'
is set.
twice, then press scroll
to set a finite number of cycles up to 999.
three times to get to the programming page,
1".
or down
to select a new program number. The
3.0   3508 Controller
until the
or
15