Operating menu
Selection
Factory setting
Switch status
Navigation
Prerequisite
Description
Selection
Factory setting
Additional information
Simulation device alarm
Navigation
Description
Selection
Factory setting
Additional information
Simulation diagnostic event
Navigation
Prerequisite
Description
Factory setting
216
• Off
• On
Off
 Expert → Diagnostics → Simulation → Switch status
Switch output simulation (→  215) = On
Define the switch state to be simulated.
• Open
• Closed
Open
The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.
 Expert → Diagnostics → Simulation → Sim. alarm
Switch alarm simulation on or off.
• Off
• On
Off
When selecting the On option, the device generates an alarm. This helps to check the
correct output behavior of the device in the case of an alarm.
An active simulation is indicated by the diagnostic message C484 Simulation failure
mode.
 Expert → Diagnostics → Simulation → Sim. diag. event
Access status display (→  149)/Access status tooling (→  148) = Service
Select diagnostic event to be simulated.
Off
Levelflex FMP51, FMP52, FMP54 PROFIBUS PA