Wiring Diagrams - Allen-Bradley SLC 500 Installation Instructions Manual

Digital
Hide thumbs Also See for SLC 500:
Table of Contents

Advertisement

Wiring Diagrams

The wiring diagrams in these installation instructions are examples only. It is not necessary to
connect an I/O device to each and every I/O module terminal.
Labeling for SLC/PLC Systems
In this document, 16-point I/O module wiring diagrams include both decimal and octal
numbers for I/O addressing and wire identification (see figure below). To wire your 16-point
I/O module when used in a SLC system, use the decimal numbers in the upper left portion of
each box. When used in a PLC system, use the octal numbers in the lower right portion of the
box.
As shipped from the factory, the I/O module has a decimal address label on the inside of its
door. A separate octal conversion kit can be ordered, to allow you to convert your module to the
octal system.
You can order the octal label kit from your Allen-Bradley Distributor. The octal kit
TIP
is ordered based on the catalog number of the I/O module.
Please refer to the SLC 500 Modular Hardware Style User Manual, publication
1747-UM011, for a listing of octal label kit catalog numbers.
IMPORTANT
Decimal and Octal Labeling for 16-point I/O Modules
For SLC (decimal)
IN 14
16
For PLC (octal)
www.aotewell.com
Be sure the octal labels are used with your PLC system. Directions on how to
install the labels are included with the kit and on page 6 of this document.
L1
100/120V AC
L2
sales@aotewell.com
1746-IA16
100/120V AC
IN 0
IN 2
IN 4
IN 6
IN 8
IN 10
IN 12
IN 14
AC COM
Internally Connected
Commons
Publication 1746-IN027D-EN-P - December 2012
Industry Automation
SLC 500 Digital I/O Modules
IN 1
0
1
IN 3
2
3
IN 5
4
5
IN 7
6
7
IN 9
10
11
IN 11
12
13
IN 13
14
15
IN 15
16
17
AC COM
SLC
PLC
+86-755-8660-6182
17