66
COM600 series, Version 5.0
Data Historian Operator's Manual
MINPT
Minimum Value of a Period, TimeStamp is the Period Time
OPTIME
Operating Time. Requires a parameter, e.g. OPTIME10MIN(>5) calculates
the time the value has been greater than 5.
PERG
Percent of Good Samples (0-1)
PERI
Percent of Invalid Samples (0-1)
RANGE
Maximum Value Within a Period minus Minimum Value Within a Period
STABILITY
Stability Graph
STARTUP
Startup Count - requires a parameter. E.g. STARTUP5MIN(>5) calculates
the number of occurrences the value has increased from less than or equal
to five to greater than five
SUM
Sum of Values Within a Period
SUMRAW
Raw Sum - Ignoring the Invalidity of Values
SUMTODOUBLE
Sum of Values Within a Period Calculated to Double - Use If There is a
Risk of Overflow
VARIANCE
Time Weighted Variance
WHEN
Conditional fetch of values. Returns requested values when given conditions
are greater than zero.
Syntax: WHEN(Class=...;Property1=...;Property2=...; ...etc... Proper-
tyN=...;xProperty=...;yProperty=...;Filter=...)
See Using the WHEN Filter for more detailed information.
Table 5.2.3-2 The set of available time identifiers
Time identifier
Description
TICKS, HUNDRED-
Hundred nanoseconds
NANOSECONDS
MICROSECOND,
Microseconds
MICROSECONDS
MS, MSEC, MILLI-
Milliseconds
SECOND, MILLI-
SECONDS
S, SECOND,
Seconds
SECONDS
MIN, MINUTE,
Minutes
MINUTES
H, HOUR, HOURS
Hours, local time
H_UTC,
Hours, UTC time
HOUR_UTC,
HOURS_UTC
D, DAY, DAYS
Days, local time
D_UTC, DAY_UTC,
Days, UTC time
DAYS_UTC
1MRS756739