Use the WEIGH-IN method for adding initial refrigerant charge, and then use SUBCOOLING method for for verifying refrigerant charge.
WEIGH-IN
CHARGING METHOD
64ºF (17.7ºC) and Below
Adjust amount for variation in
line set length and liquid line
Amount specified
diameter using table below.
on nameplate
+
Liquid Line
Set Diameter
5/16"
3/8"
1/2"
SUBCOOLING
1. THE DIAGNOSTIC SCREEN ON THE THERMOSTAT OR OUTDOOR CONTROL 7-SEGMENT DISPLAY WILL SHOW INDOOR AND
OUTDOOR MOTOR CFMS OR RPMS.
2. MEASURE OUTDOOR AMBIENT TEMPERATURE; DETERMINE WHETHER TO USE COOLING MODE OR HEATING MODE TO
CHECK CHARGE.
3. CONNECT GAUGE SET.
4. CHECK LIQUID AND VAPOR LINE PRESSURES. COMPARE PRESSURES WITH EITHER HEAT OR COOLING MODE NORMAL
OPERATING PRESSURES IN THE APPLICABLE CHARGING STICKER, NORMAL OPERATING PRESSURES, HIGH STAGE.
NOTE
DIFFERENCES MAY MEAN IMPROPER CHARGE OR OTHER SYSTEM PROBLEM.
5. SET THERMOSTAT FOR HEAT/COOL DEMAND, DEPENDING ON MODE BEING USED:
USE
USING COOLING MODE
COOLING
MODE
SUBCOOLING VALUES (SECOND STAGE - HIGH CAPACITY) IN APPLICABLE CHARGING STICKER ARE BASED ON 70 TO
80°F (21-27°C) INDOOR RETURN AIR TEMPERATURE; IF NECESSARY, OPERATE HEATING TO REACH THAT
60ºF
TEMPERATURE RANGE; THEN SET THERMOSTAT TO COOLING MODE SETPOINT TO 68ºF (20ºC) WHICH SHOULD CALL
(15ºC)
FOR SECOND-STAGE (HIGH STAGE) COOLING. WHEN PRESSURES HAVE STABILIZED, CONTINUE WITH STEP 6.
USE
HEATING
USING HEATING MODE
MODE
SUBCOOLING VALUES (SECOND-STAGE - HIGH CAPACITY) IN APPLICABLE CHARGING STICKER ARE BASED ON 65-75°F
(18-24°C) INDOOR RETURN AIR TEMPERATURE; IF NECESSARY, OPERATE COOLING TO REACH THAT TEMPERATURE
RANGE; THEN SET THERMOSTAT TO HEATING MODE SETPOINT TO 77ºF (25ºC) WHICH SHOULD CALL FOR
SECOND-STAGE (HIGH STAGE) HEATING. WHEN PRESSURES HAVE STABILIZED, CONTINUE WITH STEP 6.
6. READ THE LIQUID LINE TEMPERATURE; RECORD IN THE LIQº SPACE.
7. READ THE LIQUID LINE PRESSURE; THEN FIND ITS CORRESPONDING TEMPERATURE IN THE TEMPERATURE/ PRESSURE
CHART LISTED IN THE APPLICABLE CHARGING STICKER AND RECORD IT IN THE SATº SPACE.
8. SUBTRACT LIQº TEMPERATURE FROM SATº TEMPERATURE TO DETERMINE SUBCOOLING; RECORD IT IN SCº SPACE.
SATº
9. COMPARE SCº RESULTS WITH APPLICABLE CHARGING STICKER, BEING SURE TO NOTE ANY ADDITIONAL CHARGE FOR
LINE SET AND/OR MATCH-UP.
LIQº –
10. IF SUBCOOLING VALUE IS GREATER THAN SHOWN IN APPLICABLE CHARGING STICKER FOR THE APPLICABLE UNIT,
SCº
=
REMOVE REFRIGERANT; IF LESS THAN SHOWN, ADD REFRIGERANT.
11. IF REFRIGERANT IS ADDED OR REMOVED, REPEAT STEPS 6 THROUGH 10 TO VERIFY CHARGE.
12. DISCONNECT GAUGE SET AND RE-INSTALL BOTH THE LIQUID AND SUCTION SERVICE VALVE CAPS.
Figure 57. Using HFC-410A Subcooling Method - High Speed (High Capacity)
°F
Psig
°F
Psig
32
100.8
48
137.1
33
102.9
49
139.6
34
105.0
50
142.2
35
107.1
51
144.8
36
109.2
52
147.4
37
111.4
53
150.1
38
113.6
54
152.8
39
115.8
55
155.5
40
118.0
56
158.2
41
120.3
57
161.0
42
122.6
58
163.9
43
125.0
59
166.7
44
127.3
60
169.6
45
129.7
61
172.6
46
132.2
62
175.4
47
134.6
Total charge
=
HFC-410A
(ounces per foot)
[(Line set oz./ft. x total length) ­ (factory charge for line set)] = charge adjustment
0.40
Example: Units are factory­charged for 15 feet (4.6 meters) of 3/8" line set.
Factory charge for 3/8" is 0.60 oz/ft x 15 = 9.0 ounces.
0.60
1.00
Figure 56. Using HFC-410A Weigh-In Method
CHARGING METHOD
-
THE REFERENCE TABLE IS A GENERAL GUIDE. EXPECT MINOR PRESSURE VARIATIONS. SIGNIFICANT
— WHEN THE OUTDOOR AMBIENT TEMPERATURE IS 60°F (15°C) AND ABOVE. TARGET
— WHEN THE OUTDOOR AMBIENT TEMPERATURE IS BELOW 60°F (15°C). TARGET
.
Table 19
HFC-410A Temperature (°F) - Pressure (Psig)
°F
Psig
°F
Psig
63
178.5
79
231.6
64
181.6
80
235.3
65
184.3
81
239.0
66
187.7
82
242.7
67
190.9
83
246.5
68
194.1
84
250.3
69
197.3
85
254.1
70
200.6
86
258.0
71
203.9
87
262.0
72
207.2
88
266.0
73
210.6
89
270.0
74
214.0
90
274.1
75
217.4
91
278.2
76
220.9
92
282.3
77
224.4
93
286.5
78
228.0
NOTE - Insulate liquid line when it is routed through areas where
the surrounding ambient temperature could become higher than
the temperature of the liquid line or when pressure drop is equal
to or greater than 20 psig.
NOTE - The nameplate is shown for illustration purposes only. Go to
actual nameplate on outdoor unit for charge information.
Charging Formula for Liquid Line Charge Adjustments
(All charging MUST be performed while system is operating
either at maximum speed or 100% demand.)
°F
Psig
°F
94
290.8
110
95
295.1
111
96
299.4
112
97
303.8
113
98
308.2
114
99
312.7
115
100
317.2
116
101
321.8
117
102
326.4
118
103
331.0
119
104
335.7
120
105
340.5
121
106
345.3
122
107
350.1
123
108
355.0
124
109
360.0
77
Psig
°F
Psig
°F
365.0
141
125
445.9
370.0
126
451.8
142
375.1
127
457.6
143
380.2
128
463.5
144
385.4
129
469.5
145
390.7
130
475.6
146
396.0
131
481.6
147
401.3
132
487.8
148
406.7
133
494.0
149
412.2
134
500.2
150
417.7
135
506.5
151
423.2
136
512.9
152
428.8
137
519.3
153
434.5
138
525.8
154
440.2
139
532.4
155
140
539.0
Psig
545.6
552.3
559.1
565.9
572.8
579.8
586.8
593.8
601.0
608.1
615.4
622.7
630.1
637.5
645.0
XC20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xc20-060-230-01Xc20-024-230-01Xc20-048-230-01

Table of Contents