Daikin CHYHBH05AA Installer's Reference Manual page 103

Hybrid for multi heat pump – heat pump module
Hide thumbs Also See for CHYHBH05AA:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.2.2.B
[C-08]
External sensor
A.2.2.C
[D-0A]
External gas meter
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
LWT setpoint mode
A.3.1.1.2.1
[9-01]
Temperature range
A.3.1.1.2.2
[9-00]
Temperature range
A.3.1.1.5
[8-05]
Modulated LWT
A.3.1.1.6.1
[F-0B]
Shut-off valve
A.3.1.1.7
[9-0B]
Emitter type
└────────────────── Additional
A.3.1.2.1
LWT setpoint mode
A.3.1.2.2.1
[9-05]
Temperature range
A.3.1.2.2.2
[9-06]
Temperature range
└─ Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
A.3.2.1.2
[3-06]
Room temp. range
A.3.2.2
[2-0A]
Room temp. offset
A.3.2.3
[2-09]
Ext. room sensor offset
A.3.2.4
Room temp. step
└─ Operation range
A.3.3.1
[4-02]
Space heating OFF temp
└─ Domestic hot water (DHW)
└─ Type
A.4.1
[6-0D]
└─ Disinfection
A.4.4.1
[2-01]
Disinfection
A.4.4.2
[2-00]
Operation day
A.4.4.3
[2-02]
Start time
A.4.4.4
[2-03]
Temperature target
A.4.4.5
[2-04]
Duration
└─ Maximum setpoint
A.4.5
[6-0E]
└─ SP mode
A.4.6
└─ Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
A.4.7
[0-0C]
Weather-dependent curve
A.4.7
[0-0D]
Weather-dependent curve
A.4.7
[0-0E]
Weather-dependent curve
└─ Heat sources
└─ Boiler
A.5.2.2
[5-01]
Equilibrium temp.
└─ System operation
└─ Auto restart
A.6.1
[3-00]
└─ Averaging time
A.6.4
[1-0A]
└─ Ext amb. sensor offset
A.6.5
[2-0B]
└─ Savings mode
CHYHBH*
Minimum temp (heating)
Maximum temp (heating)
Thermo On/OFF
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (heating)
Maximum temp (heating)
DHW setpoint for high ambient temp. for DHW
WD curve.
DHW setpoint for low ambient temp. for DHW
WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Range, step
Default value
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/O
0: Not present
1: 1 /m³
2: 10 /m³
3: 100 /m³
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~80°C, step: 1°C
80°C
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0: Quick
1: Slow
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~80°C, step: 1°C
80°C
R/W
12~18°C, step: A.3.2.4
12°C
R/W
18~30°C, step: A.3.2.4
30°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: 1°C
1: 0,5°C
R/W
14~35°C, step: 1°C
25°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
0: No
1: Yes
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0~23 hour, step: 1 hour
23
R/W
fixed value
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
[E-06]=1
[E-07] ≠
40~75°C, step: 1°C, 75°C
6:
[E-07] = 6: 40~60°C, step: 1°C, 60°C
[E-06]=0
40~65°C, step: 1°C, 65°C
R/W
0: Fixed
1: Weather dep.
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-15~35°C, step: 1°C
5°C
R/W
0: No
1: Yes
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
-5~5°C, step: 0,5°C
0°C
3/6
Installer setting at variance with
default value
Date
Value
4P471775-1 - 2016.12