Preparing Refrigerant Piping; Refrigerant Piping Requirements; Refrigerant Piping Insulation - Daikin CHYHBH05AA Installer's Reference Manual

Hybrid for multi heat pump – heat pump module
Hide thumbs Also See for CHYHBH05AA:
Table of Contents

Advertisement

A (m
)
2
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5
A
Minimum floor area for hybrid unit (m
B
Total refrigerant charge in the system (kg)
H
The height measured from the floor to the bottom of the
casing. The graph is based on the height measured from
the floor to the flare nut.
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full
of water into account.
Make sure, in the event of a water leak, water cannot cause any
damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only (in a
technical room or similar) and for ambient temperatures ranging
5~30°C in heating mode.
6.3

Preparing refrigerant piping

6.3.1

Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Piping material: Phosphoric acid deoxidised seamless copper.
▪ Piping diameter:
CHYHBH05+08
Liquid piping
Gas piping
3MXM40 + 3MXM52 + 3MXM68
Liquid piping
Gas piping
4MXM68
Liquid piping
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1A – 2017.10
B (kg)
2
)
Ø6.4 mm (1/4")
Ø15.9 mm (5/8")
3× Ø6.4 mm (1/4")
1× Ø9.5 mm (3/8")
2× Ø12.7 mm (1/2")
4× Ø6.4 mm (1/4")
4MXM68
Gas piping
4MXM80
Liquid piping
Gas piping
5MXM90
Liquid piping
Gas piping
▪ Piping temper grade and thickness:
Outer diameter
Temper grade
(Ø)
6.4 mm (1/4")
Annealed (O)
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
Usage of reducers might be required based on the outdoor unit. See
"7.6.8  Usage of reducers to connect the piping to the outdoor
unit" on page 28
for more information.
6.3.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
Insulation inner
)
diameter (Ø
p
6.4 mm (1/4")
8~10 mm
9.5 mm (3/8")
10~14 mm
12.7 mm (1/2")
14~16 mm
15.9 mm (5/8")
16~20 mm
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
Use separate thermal insulation pipes for the gas and liquid
refrigerant piping.
6 Preparation
2× Ø9.5 mm (3/8")
2× Ø12.7 mm (1/2")
4× Ø6.4 mm (1/4")
1× Ø9.5 mm (3/8")
1× Ø12.7 mm (1/2")
2× Ø15.9 mm (5/8")
5× Ø6.4 mm (1/4")
2× Ø9.5 mm (3/8")
1× Ø12.7 mm (1/2")
2× Ø15.9 mm (5/8")
(a)
Thickness (t)
Ø
≥0.8 mm
t
≥1 mm
≥0.8 mm
≥1 mm
Insulation thickness
)
(t)
i
≥10 mm
≥13 mm
≥10 mm
≥13 mm
Installer reference guide
17