Measuring The Operate Value For The Negative Sequence Function - ABB RELION REC650 Commissioning Manual

650 series bay control version 2.2
Hide thumbs Also See for RELION REC650:
Table of Contents

Advertisement

Section 9
Testing functionality by secondary injection
9.4.2.2
74
Signal 3PH after about 25ms
Signal BLKU after about 50ms
Signal BLKZ after about 200ms

Measuring the operate value for the negative sequence function

Measure the operate value for the negative sequence function, if included in the
IED.
1.
Simulate normal operating conditions with the three-phase currents in phase
with their corresponding phase voltages and with all of them equal to their
rated values.
2.
Slowly decrease the measured voltage in one phase until the BLKU signal
appears.
3.
Record the measured voltage and calculate the corresponding negative-
sequence voltage according to the equation (observe that the voltages in the
equation are phasors):
3
U
=
U
+
a
2
2
L
1
EQUATION707 V2 EN-US
Where:
U
, U
and U
L1
L2
L3
IEC00000275 V1 EN-US
p ×
2
j
= ×
= -
a
1
e
0, 5
3
IECEQUATION00022 V2 EN-US
4.
Compare the result with the set value of the negative-sequence operating
voltage (consider that the set value 3U2> is in percentage of the base voltage
UBase).
5.
Repeat steps
1
and 2. Then slowly increase the measured current in one phase
until the BLKU signal disappears.
6.
Record the measured current and calculate the corresponding negative-
sequence current according to the equation (observe that the currents in the
equation are phasors):
×
=
+
×
2
3
I
I
a
I
2
L
1
L
2
IECEQUATION00021 V1 EN-US
Where:
,
I
I and I
L
1
L
2
L
3
IECEQUATION00020 V1 EN-US
U
+ ⋅
a
U
L2
L3
are the measured phase voltages
3
+
.
j
2
+ ×
a I
L
3
are the measured phase currents
1MRK 511 425-UEN A
M1405-46 v12
(Equation 1)
(Equation 2)
Bay control REC650 2.2 IEC
Commissioning manual