Error code
Description
Decimal
Hexadec
imal
■CC-Link IE Field Network Basic parameter unset
-331
FEB5H
The function is executed without setting CC-Link IE Field
Network Basic parameters.
-332
FEB4H
■Slave station timeout time specification error
■Assurance of link scan data waiting time timed out
-335
FEB1H
The specified waiting time elapsed.
-336
FEB0H
■Slave station number specification error
The specified slave station number does not exist in the
slave station.
Corrective action
Set the CC-Link IE Field Network Basic parameters with CW
Configurator.
Check the timeout time for the disconnection detection of the
specified slave station.
Increase the timeout time specified to the argument.
Check the specified slave station number.