Daikin DCM601A51 Installation Manual page 39

Intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

English
01_EN_3P291714-1.indd 39
NOTE
The "Group No. setting" menu is not displayed when the intelligent Touch Manager is
not powered on. Power on the intelligent Touch Manager and wait for a while before
trying to operate the remote controller. The "Group No. setting" menu is not displayed
also when the intelligent Touch Manager is not communicating with the indoor units
normally. Make sure that the cables are connected correctly.
3. Using the Up/Down buttons, select "Group No. setting (Group)" and press the Menu/
Enter button.
The current address setting is displayed.
<Step 3>
Group No. s e t t i n g
Group No. s e t t i n g (Group)
Group No. s e t t i n g ( U n i t )
Retur n
Setting
4. Press the Menu/Enter button to release the current address setting.
The mode indication changes from "Setting" to "Release". You are now ready to change
the DIII-NET address.
<Step 4>
Group No. s e t t i n g (Group)
Group No
Set
1-00
Retur n
Release
5. Using the Up/Down buttons, select the address you want to set.
<Step 5>
Group No. s e t t i n g (Group)
Group No
Release
1-00
Retur n
Change
6. Press the Menu/Enter button.
The DIII-NET address has been set.
<Step 6>
Group No. s e t t i n g (Group)
Group No
Set
1-03
Retur n
Release
Installation Manual 3P291714-1
DCM601A51 intelligent Touch Manager
39