5.3 Setup Menu Functions

5.3.1 Probe 1 & Probe 2 Offset
01
Probe 1 Offset
+0.0 mV
Setup Menu
Each Novatech oxygen probe has an offset calibration value printed on a tag that is attached to the probe
when it is dispatched. To achieve the most accurate measurement of oxygen the offset value must be
entered into this setup function with the same polarity as it is printed on the label. For a healthy probe the
offset value should be within ±1.0mV.
NOTE: An offset of 1.0mV will change the oxygen reading by approximately 1% oxygen when the probe is in
ambient air. However, as the process oxygen measurement drops, this offset will have a diminishing effect.
At a process gas oxygen concentration of 2%, the 1.0mV offset error will only change the reading by 0.1%
oxygen. If in any doubt about the correct offset value, set it to 0.0mV.
The function 'Probe 2 Offset' will only appear if the transmitter has been configured for 2 oxygen probes.

5.3.2 Lower Line Items

03
Lower Line Items
Probe 1 EMF
Setup Menu
This function allows the operator to change the items that are available to be displayed on the lower line of
the transmitter in Run Mode. If the word "Enabled" appears on the display for a selected lower line option,
the measurement will be available to be shown on the display in the Run Mode by scrolling through the list
∆ and D
using the D
ISPLAY
Each individual lower line measurement can be enabled or disabled by pressing the E
OPTIONS:
Temperature, Probe #1
Temperature, Probe #2
Sensor EMF, Probe #1
Sensor EMF, Probe #2
Sensor Impedance, Probe #1
Sensor Impedance, Probe #2
Oxygen, Probe #2
Oxygen, Average Probe 1 and Probe 2
Auxiliary TC Temperature
Ambient Temperature
1
Requires "Single Probe" and "Aux TC Type" to be set
Operators Manual
16
Saved
Enabled
∇ buttons.
ISPLAY
*
*
*
*
*
*
*
*
*
Options: ±6.0mV in 0.1mV increments
Default:
0.0mV
Oxygen Deficiency, Probe #1
Oxygen Deficiency, Probe #2
Combustibles, Probe #1
Combustibles, Probe #2
Carbon Dioxide, Maximum Dry, Probe #1
Carbon Dioxide, Maximum Dry, Probe #2
1
Boiler Efficiency
Flue Pressure
Burner Run Time
Service Date
button.
NTER
February 2015