Fujitsu AB*30LBAG series Service Instruction page 63

Large ceiling type inverter
Table of Contents

Advertisement

Trouble shooting 16
OUTDOOR UNIT Error Method:
Compressor rotor location cannot detect
(Permanent Stop)
Detective Actuators:
Outdoor Unit Main PCB Circuit
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure
Check Point 1 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Replace Main PCB
If Check Point 1 do not improve the symptom, change Main PCB.
Indicate or Display:
Indicate or Display:
Indoor Unit
: Operation LED: Blink, Timer LED: 13 times blink,
Vertical swing LED: OFF
Outdoor Unit : LED 13 times blink
Detective details:
While running the compressor, if the detected rotor location is out of
phase with actual rotor location more than 90 degrees,
the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If
and
repeats 5 times, the compressor stops permanently.