2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 13 : Current Release Operation Value / Release Value)
[ Heating ]
AB*30LBAG
AB*36LBAG
T0 >
16°C
=
16°C >
T0 >
5°C
=
T0 <
5°C
T0: Outdoor temperature
[ Heating ]
AB*45LBAG
T0 >
12°C
=
T0 <
12°C
T0: Outdoor temperature
[ Cooling ]
AB*30LBAG
AB*36LBAG
T0 >
45°C
=
45°C >
T0 >
38°C
=
38°C >
T0 >
19°C
=
19°C >
T0 >
13°C
=
13°C >
T0 >
=
T0 <
0°C
T0: Outdoor temperature
[ Cooling ]
AB*45LBAG
T0 >
45°C
=
45°C >
T0 >
38°C
=
38°C >
T0 >
31°C
=
31°C >
T0 >
25°C
=
25°C >
T0 >
19°C
=
19°C >
T0 >
13°C
=
T0 <
13°C
T0: Outdoor temperature
900 rpm
15.0A / 14.5A 15.0A / 14.5A
18.0A / 17.5A
18.0A / 17.5A 18.0A / 17.5A
850 rpm
23.5A / 23.0A 20.0A / 19.5A
850 rpm
10.0A / 9.5A
10.0A / 9.5A
14.0A / 13.5A 14.0A / 13.5A
18.0A / 17.5A
15.0A / 14.5A
0°C
850 rpm
12.0A / 11.5A
20.0A / 19.5A 20.0A / 19.5A
23.5A / 23.0A
Outdoor unit fan speed
780 rpm
400 rpm
13.0A / 12.5A 10.0A / 9.5A
Outdoor unit fan speed
780 rpm
350 rpm
20.0A / 19.5A 15.0A / 14.5A 12.0A / 11.5A
23.5A / 23.0A 23.5A / 23.0A 23.5A / 23.0A 23.5A / 23.0A
Outdoor unit fan speed
780 rpm
400 rpm
10.0A / 9.5A
15.0A / 14.5A
Outdoor unit fan speed
780 rpm
400 rpm
12.0A / 11.5A 12.0A / 11.5A
18.0A / 17.5A
20.0A / 19.5A
05-17
250 rpm
170 rpm
8.0A / 7.5A
18.0A / 17.5A
18.0A / 17.5A
200 rpm
150 rpm
250 rpm
170 rpm
7.0A / 6.5A
5.5A / 5.0A
7.0A / 6.5A
12.0A / 11.5A
9.5A / 9.0A
350 rpm
300 rpm
12.0A / 11.5A
12.0A / 11.5A
18.0A / 17.5A
15.0A / 14.5A
18.0A / 17.5A