Fujitsu AB*30LBAG series Service Instruction page 54

Large ceiling type inverter
Table of Contents

Advertisement

Trouble shooting 7
OUTDOOR UNIT Error Method:
INDOOR UNIT
Outdoor Discharge Pipe Temperature
Sensor Error
Detective Actuators:
Outdoor Unit Main PCB Circuit
Discharge Pipe Temperature Thermistor
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
1 2
CN21
CN22
If the voltage does not appear, replace Main PCB.
0°C
5°C
10°C
176
135
105
70°C
80°C
90°C
8.78
6.31
4.61
1 2
1 2
1 2
CN23
CN26
Indicate or Display:
Indoor Unit
: Operation LED: Blink, Timer LED: 5 times blink,
Vertical swing LED: OFF
Outdoor Unit : LED 2 times blink
Detective details:
When Discharge Pipe Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
15°C
20°C
30°C
81.8
64.5
41.1
100°C
120°C
140°C
3.43
1.98
1.21
1 2
CN25
07-08
40°C
50°C
60°C
26.9
18.1
12.5
160°C
180°C
0.77
0.51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents