5-2. HEATING OPERATION

5-2-1 HEATING CAPACITY CONTROL

A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 3 degC than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2 degC than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2 degC to -3 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on
the outdoor temperature.
( Table 2 : Compressor Frequency Range )
AB*30LBAG
AB*36LBAG
AB*45LBAG
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air
temperature
16°C
12°C
minimum
maximum
frequency
frequency
20Hz
95Hz
20Hz
95Hz
20Hz
92Hz
AB*30LBAG
C zone
AB*36LBAG
B zone
A zone
AB*45LBAG
Limit of Maximum
Frequency
A zone
95Hz
B zone
90Hz
C zone
80Hz
A zone
95Hz
90Hz
B zone
C zone
80Hz
A zone
92Hz
B zone
90Hz
C zone
80Hz