Siemens RDS110 User Manual page 34

Smart thermostat
Hide thumbs Also See for RDS110:
Table of Contents

Advertisement

Operating your thermostat from the hardware unit
6
Advanced settings
34 | 54
Siemens
Building Technologies
No. Application
Descriptions
settings
38. Heating
Indicates a different
control loop
time for PWM
(Pulse Width
Modulation) pulse
periods. You can
select the default
setting to let the
system configure
the most suitable
heating controller
settings based on
your selected
equipment type.
39. Floor
Floor temperature
temperature
limit for electric floor
limit
heating
40. Optimum start
Pre-heats the room
control setting
in an optimum way
so that you can get
the scheduled
temperature
setpoint at your
scheduled occupied
time. You can
choose Warm-up
gradient to manually
define the warm-up
speed, or choose
Self-adaptive to let
the thermostat learn
and decide the
warm-up speed.
41. Warm-up
The warm-up speed
gradient
that you set to pre-
heat the room.
Range
Factory
settings
Default
Slow
Medium
Default
Fast
2-position
Self-
adaptive
40 °C
35...60 °C Valid only if
Warm-up
Warm-up
gradient
gradient
Self-
adaptive
30 min/K
0...120 mi
n/K
A6V10877569_en--_a
Dependencies
N/A
you've
selected the
equipment type
as Electric floor
heating and
enabled the
floor
temperature
input in
Changing
system setup
[|
35].
Visible only if
you've
activated the
optimum start
control settings
in Changing
system setup
[|
35].
Valid only if
you've
activated the
optimum start
control settings
in Changing
system setup
[|
35] and
selected
Warm-up
gradient for
Application
setting No.40
2017-09-08