WIRING

Specified power cables should be used. Do not apply any
pressure on the terminals used to connect.
Incorrect connection may cause fire.
Grounding must be properly done.
The grounding cable should be kept away from gas pipes, water
pipes, telephone, lightening rods or other grounding cables.
Improper grounding may cause electric shock.
Electric Wiring must only be done by qualified professionals.
Use a separate circuit according to national regulations.
If the wiring capacity is not enough, electric shock or fire may
occur.
1.
Be sure to Install Current Leakage Protection Switch,
Or electric shock may occur.
2.
Power cable used is to be selected according to
national regulations.
3.
An all-pole disconnection device which has at least
3  mm separation distance in all pole and a residual
current device (RCD) with the rating of above 10 mA
shall be incorporated in the fixed cable shall be
installed in accordance to national wiring regulations.
4.
Outdoor unit power cable should be selected and
connected according to the outdoor unit installation
manual.
5.
Cabling should be away from high temperature
components, or the insulation layer of the cable may
be damaged.
6.
Use wire clamp to fix the cables and terminal block
after connection.
7.
Communication cables should be wrapped together
with heat insulated refrigerant pipes.
8.
Connect the indoor unit to power only after the
refrigerant has been vacuumed.
9.
Ensure the communication cable is not connected the
mains power cable.
7.1.
The specification of power
TYPE (W)
Phase
Frequency
Power
& volt
Circuit breaker/fuse (a)
Indoor unit power cable (mm
Cable size
Indoor/outdoor
(mm
)
2
connecting
cable
Electric signal
(mm
)
2
A disconnection device having an air gap contact separa-
tion in all active conductors should be incorporated in the
fixed wiring according to the National Wiring Regulation.
Ceiling-Floor Type Indoor Unit
CAUTION
Table 7-1
3600-14000W
1-PHASE
220-240V~ 50Hz
208-230V~ 60Hz
5/3
)
1.0
2
1.0
0.75
CAUTION
Power (220-240V~ 50Hz/208-230V~ 60Hz)
Power (220-240V~ 50Hz/208-230V~ 60Hz)
INDOOR UNIT
IN DOOR UNIT
IN DOOR UNIT
INDOOR UNIT
INDOOR UNIT
IN DOOR UNIT
The reserved function is indicated in broken line
table,users can select it when necessary
7.2.
Indoor/outdoor unit signal wire
• Connect the cable according to their numbers.
• Wrong connection may cause malfunction .
7.3.
Cable connection
• Ensure that the cables are protected with insulation material to
reduce condensation damage.
7.4.
Panel Wiring
Connect the Swing Motor terminal block according to the
Panel Installation Manual.
7.5.
Terminal Board Diagram
Please refer to the indoor unit wiring diagram for the wiring.
Note: The air-conditioners can connect with Central Control
Monitor (CCM). Before operation, please wiring correctly
and set system address and network address of indoor units.
Signal-phase powern supply model
L
N
To indoor power
To indoor power
220-240V ~ 50Hz
220-240V~ 50Hz
(208-230V ~ 60Hz)
(208-230V~ 60Hz)
WIRING | 9
CENTRAL CONTROL
CENTRAL CONTROL
COMPUTER
COMPUTER
MONITOR (CCM)
MONITOR(CCM)
OUTDOOR UNIT
OUTDOOR UNI T
The shield twisted-pair wire
The shield twisted-pair wire
Fig.7-1
CAUTION
To indoor power
To indoor power
220-240V ~ 50Hz
220-240V~ 50Hz
(208-230V ~ 60Hz)
(208-230V~ 60Hz)
Fig.7-2
6720874436 (2017/04)

Advertisement

Table of Contents
loading

Table of Contents