Install The Connecting Pipe | 7 - Bosch CF36-1D Installation Manual

Climate 5000 vrf system ceiling-floor type indoor unit cf series dc fan motor
Table of Contents

Advertisement

3. Hang the unit on the hanging arm by sliding backward. Securely
tighten the mounting bolts on both sides.
D. Connecting point of
D. Connecting point of
refrigerant pipe
refrigerant pipe
(D.gas side)
(D.gas side)
E. Connecting point of
E. Connecting point of
G
Drain point
Drain point
The above dimensions are based on model 36 as rated
capacity,which may differ from the unit you purchased.
4.4.
The dimension of the unit (Unit: mm)
MODEL
A
B
36~71
990
660
80~90
1280
660
1670
680
112~140
Ceiling-Floor Type Indoor Unit
Hanging
Hanging
screw bolt
screw bolt
Hanging arm
Hanging arm
Mounting bolt
Mounting bolt
refrigerant pipe
refrigerant pipe
(E.Liquid side)
(E. Liquid side)
Fig. 4-9
CAUTION
Table 4-1
C
D
E
F
203
505
506
907
203
795
506
1195
244
1070
450
1542
4.5.
Material and size of the piping
Pipe Material
Mode(R410A)
I(Liquid side)
Size(mm)
J(Gas side)
5.
INSTALL THE CONNECTING PIPE
Do not let air, dust, or other impurities fall in the pipe
system during the time of installation.
The connecting pipe should not be installed until the indoor
and outdoor units have been together.
Keep the connecting pipe dry, and do not let moisture in
during installation.
The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper tube.
5.1.
The Procedure of Connecting Pipes
5.1.1
Measure the necessary length of the connecting pipe, and
use the following process.
1) Connect the indoor unit at first, then the outdoor unit. a. Use a pipe
bender to form the radius of the pipework.
1. Cover the surfaces of the flare pipe and the joint nuts
with oil, and tighten it for 3~4 turns with hands before
fasten the flare nuts.
2. Be sure to use two wrenches simultaneously when you
connect or disconnect the pipes
2) The stop valve of the outdoor unit should be closed tightly (as
original supplied). Every time you operate it, first loosen the nuts
at the part of stop valve, then connect the flare pipe immediately
(within 5 minutes). If the nuts have been loosened for a long time,
dust and other impurities may enter the pipe system and may cause
malfunction later. Ensure that air is expelled from out of the pipe
with refrigerant before connection.
3) Remove the air (refer to the "Expel The Air") after connecting the
refrigerant pipe with the indoor unit and the outdoor unit. Then
fasten the nuts at the service-points.
G
Notices For Benable pipe.
200
• The bending angle should not exceed 90°.
200
• Bending position is preferably in the bendable pipe. The larger
200
the better it is.
• Do not bend the pipe more than three times.

INSTALL THE CONNECTING PIPE | 7

Table 4-2
Copper Pipe for Air Conditioner
36~45
56~140
Ø 6.4
Ø 9.5
Ø 12.7
Ø 15.9
CAUTION
CAUTION
6720874436 (2017/04)

Advertisement