Bosch CF36-1D Installation Manual
Bosch CF36-1D Installation Manual

Bosch CF36-1D Installation Manual

Climate 5000 vrf system ceiling-floor type indoor unit cf series dc fan motor

Advertisement

Quick Links

Climate 5000 VRF
Ceiling-Floor Type Indoor Unit
CF Series - DC Fan Motor
Installation manual
CF36-1D
CF80-1D
CF45-1D
CF90-1D
CF56-1D
CF112-1D
CF71-1D
CF140-1D
Thank you very much for purchasing our air conditioner,
Before using your air conditioner, please read this manual carefully and keep it for future reference.

Advertisement

Table of Contents
loading

Summary of Contents for Bosch CF36-1D

  • Page 1 Climate 5000 VRF Ceiling-Floor Type Indoor Unit CF Series - DC Fan Motor Installation manual CF36-1D CF80-1D CF45-1D CF90-1D CF56-1D CF112-1D CF71-1D CF140-1D Thank you very much for purchasing our air conditioner, Before using your air conditioner, please read this manual carefully and keep it for future reference.
  • Page 2 2 | NOTES 6720874436 (2017/04) Ceiling-Floor Type Indoor Unit...
  • Page 3: Table Of Contents

    PRECAUTIONS | 3 CONTENTS PAGE Install according to these installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock PRECAUTIONS ....... . . 3 and fire.
  • Page 4: Installation Information

    4 | INSTALLATION INFORMATION INSTALLATION INFORMATION If the refrigerant leaks during installation, ventilate the area im- mediately. Toxic gas may be produced if the refrigerant comes into the place ■ To install properly, please read this "installation manual" at contacting with fire. first.
  • Page 5: Indoor Unit Installation

    INDOOR UNIT INSTALLATION | 5 INDOOR UNIT INSTALLATION Remote controller & Its Frame 1. Remote controller ....1 4.1 The units may be mounted vertically, provided that the correct clearances for positioning are maintained.
  • Page 6 6 | INDOOR UNIT INSTALLATION 1. Connect the hook with self tapping screw onto the wall. 4.3. Ceiling Installation (Refer to Fig. 4-4) Hook Hook Tapping screw Tapping screw Washer Washer Hanging arm Hanging arm Fig.4-5 ■ Remove the side board and the grill. (Refer to Fig. 4-6) <6mm <...
  • Page 7: Install The Connecting Pipe | 7

    INSTALL THE CONNECTING PIPE | 7 3. Hang the unit on the hanging arm by sliding backward. Securely 4.5. Material and size of the piping tighten the mounting bolts on both sides. Table 4-2 Hanging Hanging Pipe Material Copper Pipe for Air Conditioner screw bolt screw bolt Mode(R410A)
  • Page 8: Connect The Drain Pipe

    8 | CONNECT THE DRAIN PIPE ■ CONNECT THE DRAIN PIPE Bend the connecting pipe of small wall thickness. • Cut out a desired concave at the bending part of the insulating pipe. 6.1. Install the drainpipe of the indoor unit •...
  • Page 9: Wiring

    WIRING | 9 WIRING Power (220-240V~ 50Hz/208-230V~ 60Hz) Power (220-240V~ 50Hz/208-230V~ 60Hz) ■ Specified power cables should be used. Do not apply any pressure on the terminals used to connect. Incorrect connection may cause fire. INDOOR UNIT IN DOOR UNIT ■...
  • Page 10: Control Operation

    10 | CONTROL OPERATION CAUTION The system together can have 64 units (0-63),everyone has only system address code. If two addresses are the same in one system, a abnormal operation will occur. Please switch off the power before setting,otherwise the TO CCM TO CCM TO INDOOR&OUTDOOR...
  • Page 11 CONTROL OPERATION | 11 Table 8-2 Type Contents LED lamp flash Remarks The evaporator sensor check point is adnormal or After the malfunctions disappear, it Malfunction Run lamp flashes quickly. room temp. sensor is abnormal. restores automatically. After the malfunctions disappear, it Malfunction Indoor/outdoor unit communication is abnormal.
  • Page 12 12 | CONTROL OPERATION SW5 definition S W 5 ■ ■ means temperature means temperature compensation is 6 degrees compensation is 4 degrees under heating mode under heating mode S W 5 ■ ■ means temperature means temperature compensation is 2 degrees compensation is 8 degrees under heating mode under heating mode...
  • Page 13: Test Operation

    TEST OPERATION | 13 TEST OPERATION The test operation must be carried out after the entire installation has been completed. Please confirm the following points before the test operation: • The indoor unit and outdoor unit are installed properly. • Pipe work and wiring are correctly installed. •...
  • Page 14 14 | NOTES 6720874436 (2017/04) Ceiling-Floor Type Indoor Unit...
  • Page 15 NOTES | 15 Ceiling-Floor Type Indoor Unit 6720874436 (2017/04)
  • Page 16 Robert Bosch (Pty) Ltd., 15th Road, Randjespark 1685 Midrand SOUTH AFRICA...

Table of Contents