Installation; Description, In General - Danfoss ECL Comfort 210 Operating Manual

Floor (screed) drying program
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program

2.0 Installation

2.1 Description, in general

Application keys for the ECL Comfort 210 / 296 / 310 series, which
control heating circuits, offer a floor drying program, also called
screed drying program.
The floor drying program is used after a new floor heating circuit
has been placed and fresh-from-factory concrete covers the floor
heating pipes. The floor drying program can also be used, when
the self-leveling screed has been distributed.
The floor drying program can be started immediately in order to
dry-out the concrete / screed according to a set time / temperature
plan.
Navigation to the menu for 'Floor drying':
Common controller > MENU > Floor drying:
Functional heating:
The flow temperature is controlled
according to a set time / temperature plan
in order to dry-out the concrete / screed.
Curing heating:
The flow temperature is controlled
according to a set time / temperature plan
in order to cure the concrete / screed. The
curing must be done before mounting of,
for example, tiles.
Functional and curing heating can work as one process or
separated.
The time / temperature plan is set and is common for selected
circuits.
VI.JM.P2.02
= Time
T
= Functional heating
# 1 #
= Curing heating
# 2 #
© Danfoss | 2017.08 | 5