SW2 setting
Display contents
Indoor unit control
status
Indoor 1, 2
1 2 3 4 5 6
ON
OFF
Indoor unit control
status
Indoor 3, 4
1 2 3 4 5 6
ON
OFF
Condenser/evaporater
temperature (TH3)
1 2 3 4 5 6
ON
OFF
Outdoor unit control
status
1 2 3 4 5 6
ON
OFF
Discharge super heat
SHd
0 - 216
Cooling: Outdoor TH2 -
1 2 3 4 5 6
ON
OFF
Heating: Outdoor TH2
Sub cool Sc
0 - 130
Cooling: Outdoor TH3
1 2 3 4 5 6
ON
OFF
Heating: Indoor TH3
Target sub cool step N
1 2 3 4 5 6
ON
1 - 5
OFF
Control mode display system
Indoor unit No.2
Indoor unit No.4
–39 - 88
(When 0 °C or lower, "–"and temperature are displayed
alternately.)
<Example> When –10,
Control mode display system
Indoor unit No.2
Indoor unit No.4
0 - 216
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
<Example> When 150,
Outdoor TH3
- Indoor TH3
(Average)
0 - 130
(When 100 or higher, 100s digit and 10s and units digits
are displayed alternately.)
- Outdoor
<Example> When 100,
TH1
(Average) -
Indoor TH2
(Average)
1 - 5
Description of display
Indoor unit No.1
Indoor unit No.3
Control mode
Display
Indoor unit
0
Ordinary
Hot adjustment
1
2
Defrosting
3
4
Heater ON
Freeze prevention
5
6
Surge prevention
Compressor OFF
7
every other second
←→ –10
Indoor unit No.1
Indoor unit No.3 Outdoor unit
Control mode
Display
Indoor unit
Ordinary
0
1
Hot adjustment
Defrosting
2
3
Heater ON
4
5
Freeze prevention
Surge prevention
6
7
Compressor OFF
every other second
←→ 50
1
every other second
←→ 00
1
–32–
Unit
Outdoor unit
°C
Outdoor unit
°C
°C