CONTROL PANEL

6.1.

Functions of the logical programmer

The logical programmer Siemens serie LOGO handles the logical working of the whole unit.
Its display allow the visualization of the status of the logical inputs (marked as I), the logical
outputs (marked as Q), current time and date, the several messages enabled by the
programme.
It is also possible to modify the settings of the entered numerical parameters (marked as B).
The numbering of the inputs and outputs is arranged on several rows, each of them
correspond to a ten (I1÷I9, I10÷I19 ecc.).
By pushing the buttons
service : current time and date, inputs, outputs, (M, to be ignored), function buttons (ESC+C..).
By pushing the buttons
The used functions are the following :
MARK
DESCRIPTION
I1
button START
I2
input available for regeneration inhibit
I3
button RESET
I4
input for low level in the water storage tank
I5
input for high level in the water storage tank
I6
input for water supply inhibit
I7 (AI1)
pressure sensor INLET (P-IN for DP and DP-DUAL version
I8 (AI2)
pressure sensor OUTLET (P-OUT for DP and DP-DUAL version
Q1
output of the solenoid valve E1 (E1A for -DUAL versions)
Q2
output of the solenoid valve E2 (E2A for -DUAL versions)
Q3
output of the solenoid valve E3 (E3A for -DUAL versions)
Q4
output of running regeneration (column A for -DUAL versions)
Q5
output related to solenoid valve E1B (for -DUAL versions only)
Q6
output related to solenoid valve E2B (for -DUAL versions only)
Q7
output related to solenoid valve E3B (for -DUAL versions only)
Q8
output related to report of running regeneration column B (for -DUAL versions
B1
time of BACKWASHING
B2
time of RINSING
B3-1
setting time and days of regeneration
B3-4
ON = switching pulse function of parameters B3-1, B3-2 and B3-3
B4
delay of driving of end-cycle
B5
max allowable pressure drop
B6
time of delay starting regeneration of column B after column A (for -DUAL versions only)
B19
working mode selection DT / DP
B100
ON = message in ITALIAN
All settings of automatic working are factory-made at the shipment.
See the chapter "SETTINGS" to check the factory-set.
s.r.l.Milano - ITALY
INSTRUCTIONS MANUAL AUTOMATIC FILTERS
or
the display shows, alternatively, the visualizations of the
and
the messages enabled by the programme are visualized.
OFF = message in ENGLISH
Page 14 of 23
FCD-FACD-FFD /DT /DP /DT-DUAL /DP-DUAL
)
only
)
only
fcd-dp_mi-r4.doc –
)