Troubleshooting; Led Indications - Siemens QUADLOG Installation And Service Instructions Manual

Critical analog input module
Hide thumbs Also See for QUADLOG:
Table of Contents

Advertisement

Maintenance
Cleaning a CAI/SAI Marshalled Termination Assembly involves careful brushing and vacuuming to
remove accumulated dust and dirt harboring chemical particulate that can accelerate terminal or connector
contact corrosion. When cleaning the termination hardware area, be careful not to disturb the wiring.
Electrical shock hazard. Remove power from all involved wires and terminals.

3.4 Troubleshooting

A module's operating status and errors are indicated by its status LEDs. Also, error codes and related
diagnostic messages are displayed by the 4-mation configuration software and the Diagnostic Logger
utility. Details of error codes and messages are available in the following documents:
4-mation Software Messages and Error Codes (document number CG39-21, located in binder
UM39-11)
Module Diagnostic Error Codes (document number CG39-19, located in binder UM39-14)
Module status LEDs are located on the CAI's bezel. Note LED indications, then refer to Table 3-1 for
CAI status and the listed documents to determine the appropriate course of action.
Interconnect I/O Cable pin assignments for CAI applications are provided in Table 2–2. These are
provided for troubleshooting a suspect cable. As necessary, check field wiring and field-located devices.
LED
LED INDICATION
OK
Black (Off)
OK
Solid Green
OK
Flashing Green/ Black
OK
Solid Red
OK
Flashing Red/ Green
OK
Flashing
(1/sec.)Red/Black
OK
Flashing
(5/sec.)Red/Black
Solid Green
ACTIVE
Black (Off)
3-2
WARNING
Table 3–1 LED Indications
MODULE STATUS
No 24V power input to module
Module on-board power supply failure
Module OK. Configured, with no
faults or failures.
Module not configured. No faults or
failures.
Module severe failure
Class 2 error detected
Class 3 error detected
IOBUS communications error
Module in Control (calculate mode)
Module in verify mode (or off-line)
ACTION
Troubleshoot or replace 24V power
supply
Properly seat the module
Replace module
Normal, no action required.
Download configuration
Replace module
Check 4-mation error description
(user action).
Check 4-mation error description
(user action).
Check control module
Check IOBUS cables
Replace module
SDQLCAI-1
May 2002