Preparing The Site; Temperature Requirements; Humidity Requirements - Cisco Nexus 93180YC-FX Hardware Installation Manual

Hide thumbs Also See for Nexus 93180YC-FX:
Table of Contents

Advertisement

Preparing the Site

Temperature Requirements

The switch requires an operating temperature of 32 to 104 degrees Fahrenheit (0 to 40 degrees Celsius). If
the switch is not operating, the temperature must be between –40 to 158 degrees Fahrenheit (–40 to 70 degrees
Celsius).

Humidity Requirements

High humidity can cause moisture to enter the switch. Moisture can cause corrosion of internal components
and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size.
The switch is rated to operate at 8- to 80-percent relative humidity, with a humidity gradation of 10 percent
per hour. For nonoperating conditions, the switch can withstand from 5- to 95-percent relative humidity.
Buildings in which the climate is controlled by air-conditioning in the warmer months and by heat during the
colder months usually maintain an acceptable level of humidity for the switch equipment. However, if the
Temperature Requirements, page 5
Humidity Requirements, page 5
Altitude Requirements, page 6
Dust and Particulate Requirements, page 6
Minimizing Electromagnetic and Radio Frequency Interference, page 6
Shock and Vibration Requirements, page 7
Grounding Requirements, page 7
Planning for Power Requirements, page 7
Airflow Requirements, page 8
Rack and Cabinet Requirements, page 9
Clearance Requirements, page 9
C H A P T E R
Cisco Nexus 93180YC-FX NX-OS Mode Switch Hardware Installation Guide
2
5

Advertisement

Table of Contents
loading

Table of Contents