Preparing the Site
•
•
•
•
Temperature Requirement
This switch is rated to operate at 32 to 104°F (0 to 40°C). It can be stored at -40 to 158°F (-40 to 70°C).
Humidity Requirement
High humidity can cause moisture to enter the switch. Moisture can cause corrosion of internal components
and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size.
The switch is rated to withstand from 5- to 95-percent (nonoperating) and 5- to 90-percent (operating) relative
humidity.
Buildings cooled with air conditioning during warm months and warmed during cold months usually maintain
an acceptable level of humidity. However, if the site is unusually humid, use a dehumidifier to maintain the
required humidity level.
Altitude Requirements
High-altitude (low-pressure) conditions outside of 0 to 5,000 feet (0 to 1524 m) can reduce the cooling
efficiency and cause electrical problems.
Dust and Contaminants
To prevent contaminant buildup and increased internal chassis temperatures, make sure that the operating
environment is as clean as possible and free of dust and other contaminants. Do not permit smoking, food, or
drinks near the switch.
Temperature Requirement, on page 5
Humidity Requirement, on page 5
Altitude Requirements, on page 5
Dust and Contaminants, on page 5
2
C H A P T E R
Cisco Nexus 3600 Hardware Installation Guide
5