Cisco Nexus 93180YC-FX Hardware Installation Manual page 13

Hide thumbs Also See for Nexus 93180YC-FX:
Table of Contents

Advertisement

Overview
3
L1 (software defined port)
4
L2 (software defined port)
5
Chassis LEDs (Beacon [BCN] and Status [STS])
Note
USB support is limited to USB 2.0 devices that use less than 2.5 W (less than 0.5 A inclusive of surge
current). Devices, such as external hard drives, that instantaneously draw more than 0.5 A are not supported.
Depending on whether you plan to position the ports in a hot or cold aisle, you can order the fan and power
supply modules with port-side intake or port-side exhaust airflow. To determine the airflow direction of the
modules installed in your switch, see the following table.
Replaceable Modules
Fans
AC power supplies
HVAC/HVDC power supplies
DC power supplies
The fan and power supply modules are field replaceable and you can replace one fan module or one power
supply module during operations so long as the other modules are installed and operating. If you have only
one power supply installed, you can install the replacement power supply in the open slot before removing
the original power supply.
All of the fan and power supply modules must have the same direction of airflow. Otherwise, the switch
Note
can overheat and shut down. If you are installing a dual-direction power supply, that module will
automatically use the same airflow direction as the other modules in the switch.
Caution
If the switch has port-side intake airflow (burgundy coloring for fan modules), you must locate the ports
in the cold aisle. If the switch has port-side exhaust airflow (blue coloring for fan modules), you must
locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut
down.
The switch supports the following Fabric Extenders (FEXs):
• N2K-C2224TP
• N2K-C2232PP
• N2K-C2232TM
8
Out-of-band management port (RJ-45 port)
9
Screw holes (6) for attaching rack mounting
brackets
10
Screw holes (2) for attaching grounding lug.
Port-Side Intake Airflow Coloring
Burgundy
Burgundy
Burgundy
Cisco Nexus 93180YC-FX NX-OS Mode Switch Hardware Installation Guide
Overview
Port-Side Exhaust Airflow Coloring
Blue
Blue
White
Blue
3