1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed. ...
Page 4
WARNING Do not perform flare connection inside a building or dwelling or room, when joining the heat exchanger of indoor unit with interconnecting piping. Refrigerant connection inside a building or dwelling or room must be made by brazing or welding. Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a building or dwelling or room.
Page 5
CAUTION Select an installation location which is easy for maintenance. Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property. Power supply connection to the room air conditioner. Use power supply cord 3 x 1.5 mm (1.0 ~ 1.5HP), type designation 60245 IEC 57 or heavier cord.
2. Precaution for Using R32 Refrigerant The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
Page 7
CAUTION 2-5. No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. He/She must not be smoking when carrying out such work.
Page 8
CAUTION Leak detection methods Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re- calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. ...
Page 9
CAUTION Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. Recovery ...
3. Specifications Indoor CS-CZ9SKE CS-CZ12SKE Model Outdoor CU-CZ9SKE CU-CZ12SKE Performance Test Condition EUROVENT EUROVENT Phase, Hz Single, 50 Single, 50 Power Supply Min. Mid. Max. Min. Mid. Max. 0.85 2.50 3.00 0.85 3.50 4.00 Capacity BTU/h 2900 8530 10200 2900...
Page 11
Indoor CS-CZ9SKE CS-CZ12SKE Model Outdoor CU-CZ9SKE CU-CZ12SKE Type Hermetic Motor / Rotary Hermetic Motor / Rotary Compressor Motor Type Brushless (4-poles) Brushless (4-poles) Output Power Type Cross-Flow Fan Cross-Flow Fan Material ASG20K1 ASG20K1 Motor Type DC / Transistor (8 poles)
Page 12
Indoor CS-CZ9SKE CS-CZ12SKE Model Outdoor CU-CZ9SKE CU-CZ12SKE Weight Net (I/D / O/D) kg (lb) 8 (18) / 36 (79) 8 (18) / 36 (79) Stacking No. (CS / CU / CZ) Actual Stacking Condition (12 / 6 / -) Actual Stacking Condition (12 / 6 / -)
4. Features Inverter Technology Wider output power range Energy saving More precise temperature control Environment Protection Non-ozone depletion substances refrigerant (R32) Long Installation Piping Long piping up to 20 meters Easy to use remote control Quality Improvement Random auto restart after power failure for safety restart operation Gas leakage protection...
5. Location of Controls and Components Indoor Unit Air Filters Auto OFF/ON button • Use when remote control is misplaced Front panel or malfunction occurs. Aluminium Fin INDICATOR (Green/ POWER/ DEICE Blue) TIMER (Orange) Horizontal Airflow +8/15°C (Green) direction louver Remote Control HEAT •...
6. Dimensions Indoor Unit & Remote Control <Top View> <Side View> <Side View> Air intake <Front View> direction Air outlet Right direction piping Left hole piping hole <Bottom View> <Remote Control> <Rear View> 41-61 <Remote Control Holder> Gas side Liquid side Relative position between the indoor unit and the installation plate <Front View>...
Outdoor Unit <Top View> Space necessary for 68.5 installation (124) (53.4) 100mm 100mm 100mm Anchor Bolt Pitch 330 × 540 <Side View> <Side View> <Front View> 3-way valve at Gas side 2-way valve at Liquid side Unit : mm (Low Pressure) (High Pressure)
Outdoor Unit YELLOW (YEL) SINGLE PHASE BLUE (BLU) RED (RED) TO INDOOR UNIT POWER SUPPLY (BLK) (WHT) (RED) (TRADEMARK) REACTOR COMPRESSOR TERMINAL THE PARENTHESIZED LETTERS IS TERMINAL INDICATED ON TERMINAL COVER. (BLK) (WHT) (RED) BOARD ELECTRONIC CONTROLLER RAT1 RAT2 (GRY) (GRY) OUTDOOR AIR TEMP.
12. Installation Instruction 12.1 Select the Best Location 12.1.1 Indoor Unit 12.1.3 Indoor/Outdoor Unit Installation Diagram Do not install the unit in excessive oil fume area such as kitchen, workshop and etc. There should not be any heat source or steam WARNING near the unit.
12.2 Indoor Unit 12.2.1 How to Fix Installation Plate The mounting wall shall be strong and solid enough to prevent it from vibration. Wall Wall Wall More than 1 More than 1 Indoor unit More than 2 screw Installation plate 1 228 mm (1.0~1.5HP) 241.5 mm (2.0HP) Measuring...
Page 28
12.2.3 Indoor Unit Installation • Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage. • Use shock absorber during pull out the piping to protect the intake grille from damage. Piping Piping Shock absorber...
Exchange the drain hose and cap Rear view for left piping installation Connection cable Piping Drain hose More than 950 mm Connection cable Drain hose Drain cap Adjust the piping slightly Drain hose downwards. Sleeve for piping hole • • How to pull the piping and drain hose out, in case of the In case of left piping how to insert the embedded piping.
Page 30
Terminal Board Tape Earth Wire longer than others AC Connection cable wires for Indoor & outdoor safety reason connection cable Escapement Holder Indoor & outdoor Recommended connection cable length (mm) Outdoor unit Recommended length (mm) 35 35 35 55 WARNING This equipment must be properly earthed.
12.3 Outdoor Unit 12.3.1 Install the Outdoor Unit After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm). When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt, screws or nails.
AIR PURGING METHOD IS PROHIBITED FOR R32 SYSTEM 12.3.3 Evacuation of the Equipment WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation. There is no extra refrigerant in the outdoor unit for air purging.
12.3.4 Connect the Cable to the Outdoor Unit Remove the control board cover from the unit by loosening the screw. Cable connection to the power supply through Isolating Devices (Disconnecting means). Connect approved type polychloroprene sheathed power supply cord 3 x 1.5 mm type designation 60245 IEC 57 or heavier cord to the terminal board, and connect the others end of the cord to Isolating Devices (Disconnecting means).
Page 34
12.3.6 Outdoor Unit Drain Water Water will drip from the base pan hole area during defrost function. To avoid water dripping, do not stand or place objects at this area. Hole 12.3.7 Check the Drainage Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) ...
13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
Page 36
2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
Page 38
3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
Page 39
7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
Page 40
11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
Page 44
13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
Page 45
13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
Page 46
13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
Page 48
2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
Page 49
13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
Page 50
13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
Page 51
13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
Page 52
(Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
Page 54
1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
14. Operation Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
14.1.5 Automatic Operation This mode can be set using remote control and the operation is decided by remote control setting temperature, remote control operation mode and indoor intake air temperature. During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the indoor intake air temperature.
ii Auto Fan Speed [Cooling, Dry] According to room temperature and setting temperature, indoor fan speed is determined automatically. When set temperature is not achieved, the indoor fan will operate according to pattern below. When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically. [Fan] ...
14.4.1 Vertical Airflow Vane Angle (°) Operation Mode Usual (Ventilation) 10 ~ 40 Auto Control with dew 10 ~ 40 Cooling, Fan Usual (Ventilation) 17.5 32.5 Manual Control with dew 17.5 32.5 Usual 10 ~ 40 Auto Control with dew 10 ~ 40 Usual 17.5...
14.5 Timer Control There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time. If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence. 14.5.1 ON Timer Control ...
14.8 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode) A. Purpose To provide quiet cooling operation compare to normal operation. B. Control condition a. Quiet operation start condition When “POWERFUL/QUIET” button at remote control is pressed twice. QUIET will be shown on remote control display. b.
14.11 +8/15°C Heat Operation +8/15°C Heat operation provides heating at low setting temperature in unoccupied houses during winter for the purpose of protecting equipments or housing appliances which may be destroyed by the extreme cold weather. This operation can be ON by pressing the +8/15°C heat button on the remote control. ...
15. Protection Control 15.1 Protection Control for All Operations 15.1.1 Restart Control (Time Delay Safety Control) The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period. ...
Page 63
15.1.4 Compressor Overheating Prevention Control Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency are as below. If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes, timer LED will be blinking.
15.2 Protection Control for Cooling & Soft Dry Operation 15.2.1 Outdoor Air Temperature Control The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 1 minute after the compressor starts. ...
15.2.6 Odor Cut Control To reduce the odor released from the unit. Start Condition AUTO FAN Speed is selected during COOL or DRY operation. During freeze prevention control and timer preliminary operation, this control is not applicable. Control content ...
16. Servicing Mode 16.1 Auto OFF/ON Button AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be used to operate air conditioner with limited function if remote control is misplaced or malfunction. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5 seconds.
REMOTE CONTROL RECEIVING SOUND OFF/ON MODE The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset”...
Page 68
Auto restart enable/disable selection Normal display mode Press SW to enter customer zone & press SW’s to choose function 10 Control Disable Transmit “Enable or Disable” code Control Enable 1 Press SW, special setting is immediately cancelled and normal mode starts. 2 If no SW is pressed for 30secs, then special setting mode is cancelled and normal mode starts.
Page 69
New Deice Judgement Selection Normal display mode Press SW (t 0secs) When SW pressed continuously for t 5secs to enter service zone & press SW’s to choose function 60 Switching = No Transmit “No or Yes” code Switching = Yes Note: By default is New Deice Judgement.
17. Troubleshooting Guide 17.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that Normal Pressure and Outlet Air Temperature (Standard) there are no electrical problems before inspecting the Gas pressure Outlet air refrigeration cycle. MPa (kg/cm temperature (°C) Such problems include insufficient insulation, problem Cooling Mode 0.9 ~ 1.2 (9 ~ 12)
17.2 Relationship Between the Condition of the Air Conditioner and Pressure and Electric Current Cooling Mode Heating Mode Condition of the Electric current Electric current air conditioner Low Pressure High Pressure Low Pressure High Pressure during operation during operation Insufficient refrigerant ...
17.3 Breakdown Self Diagnosis Function 17.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) Every press of the button (up or down) will Once abnormality has occurred during operation, increase abnormality numbers and transmit the unit will stop its operation, and Timer LEDs abnormality code signal to the main unit.
17.4 Error Codes Table Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation No memory of failure — Normal operation — — Indoor fan only Indoor/outdoor wire terminal Indoor/outdoor operation can Indoor/outdoor After operation for ...
Page 74
Diagnosis Abnormality / Abnormality Protection Problem Check location display Protection control Judgment Operation Check indoor/outdoor Wrong wiring and connection wire and connection Abnormal wiring or — — connecting pipe, expansion pipe piping connection valve abnormality Expansion valve and lead wire and connector ...
17.5 Self-diagnosis Method 17.5.1 H11 (Indoor/Outdoor Abnormal Communication) Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused Faulty indoor unit PCB.
Page 76
17.5.2 H12 (Indoor/Outdoor Capacity Rank Mismatched) Malfunction Decision Conditions During startup, error code appears when different types of indoor and outdoor units are interconnected. Malfunction Caused Wrong models interconnected. Wrong indoor unit or outdoor unit PCBs mounted. ...
Page 77
17.5.3 H14 (Indoor Intake Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 78
17.5.4 H15 (Compressor Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. Faulty sensor.
Page 79
17.5.5 H16 (Outdoor Current Transformer) Malfunction Decision Conditions An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes. Malfunction Caused Lack of gas Broken CT (current transformer) ...
Page 80
17.5.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused ...
Page 81
17.5.7 H23 (Indoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 82
17.5.8 H27 (Outdoor Air Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 83
17.5.9 H28 (Outdoor Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 84
17.5.10 H30 (Compressor Discharge Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 85
17.5.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection.
Page 86
17.5.12 H33 (Unspecified Voltage between Indoor and Outdoor) Malfunction Decision Conditions The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused Wrong models interconnected. Wrong indoor unit and outdoor unit PCBs used. Indoor unit or outdoor unit PCB defective.
Page 87
17.5.13 H34 (Outdoor Heat Sink Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 88
17.5.14 H36 (Outdoor Gas Pipe Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 89
17.5.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality) Malfunction Decision Conditions During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors. Malfunction Caused Faulty connector connection. ...
Page 90
17.5.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked) Malfunction Decision Conditions The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor. Malfunction Caused Operation stops due to short circuit inside the fan motor winding. ...
Page 91
17.5.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing) Malfunction Decision Conditions Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation. ...
Page 92
17.5.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry) Error Code will not display (no Timer LED blinking) but store in EEPROM Malfunction Decision Conditions Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C) Malfunction Caused ...
Page 93
17.5.19 F11 (4-way valve Abnormality) Malfunction Decision Conditions When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during cooling and compressor operating, the 4-way valve is detected as malfunction. Malfunction Caused ...
Page 94
17.5.20 F17 (Indoor Standby Units Freezing Abnormality) Malfunction Decision Conditions When the different between indoor intake air temperature and indoor pipe temperature is above 10°C or indoor pipe temperature is below -1.0°C. Remark: When the indoor standby unit is freezing, the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit(s).
Page 95
17.5.21 F90 (Power Factor Correction Protection) Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification. Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
Page 96
17.5.22 F91 (Refrigeration Cycle Abnormality) Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency. Malfunction Caused Lack of gas. 3-way valve close. Troubleshooting...
Page 97
17.5.23 F93 (Compressor Rotation Failure) Malfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused Compressor terminal disconnect Faulty Outdoor PCB Faulty compressor Troubleshooting When F93 indication happens For safety reason and to prevent component breakdown, always switch off the power before...
Page 98
17.5.24 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry) Malfunction Decision Conditions During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by the outdoor unit heat exchanger thermistor. Malfunction Caused ...
Page 99
17.5.25 F96 (IPM Overheating) Malfunction Decision Conditions During operating of cooling and heating, when IPM temperature data (120°C) is detected by the IPM temperature sensor. Multi Models Only Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated. Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is detected by the heat sink temperature sensor.
Page 100
17.5.26 F97 (Compressor Overheating) Malfunction Decision Conditions During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor. Malfunction Caused Faulty compressor tank temperature sensor 2/3 way valve closed ...
Page 101
17.5.27 F98 (Input Over Current Detection) Malfunction Decision Conditions During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Page 102
17.5.28 F99 (DC Peak Detection) Malfunction Decision Conditions During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry. Malfunction Caused DC current peak due to compressor failure. ...
18. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 18.1 Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor Removal Procedures 18.1.1...
Page 104
Pull out the main Detach connectors as labeled from the electronic controller electronic controller, then pull out the electronic controller gently. halfway. AC303 Detach the Earth wire screw, terminal wire (BL), terminal wire (RED) and earth wire screw (Green). CN-FM Detach the CN-DISP connector then remove the indicator PCB complete.
18.1.4 To Remove Control Board 12. Remove 4 screws holding the control board together then pull out the control board. Figure 6 18.1.5 To Remove Cross Flow Fan and Indoor Fan Motor Remove the screw that holds the cross flow fan and the fan motor shaft. Figure 7 Holdfast Remove the bearing by pulling...
Page 106
16. Push the holdfast to the left and lift up the evaporator. Evaporator 17. Remove the cross flow fan from 18. Fan motor can be removed after the the unit by pulling it to the left and removal of cross flow fan. downward.
18.2 Outdoor Electronic Controller Removal Procedure Caution! When handling electronic controller, be careful of electrostatic discharge. 1. Remove the 5 screws of the Top Panel. 5. Remove the Control Board as follows: Fig. 1 Fig. 4 2. Remove the 8 screws of the Front Panel. Fig.
Technical data provided are based on the air conditioner running under free frequency. 19.1 Cool Mode Performance Data Unit setting: Standard piping length, Hi Fan, Cool mode at 16°C Voltage: 230V 19.1.1 CS-CZ9SKE/CU-CZ9SKE Indoor (°C) Outdoor DB (°C) 19.0 2699...
Indoor room temperature: 20°C DryBulb/ -°C Wet Bulb Unit setting: Standard piping length, forced heating at 30°C, Hi fan Compressor frequency: Rated for Heating operation Piping length: 5m Voltage: 230V 20.2.1 CS-CZ9SKE CU-CZ9SKE Outdoor Air Temperature (°C) 3.70 3.20 2.70 2.20 1.70...
Page 113
20.2.2 CS-CZ12SKE CU-CZ12SKE Outdoor Air Temperature (°C) 5.00 4.50 4.00 3.50 3.00 2.50 2.00 1.50 Outdoor Air Temperature (°C) Outdoor Air Temperature (°C)
21. Exploded View and Replacement Parts List 21.1 Indoor Unit CWH55025J CWH55051J Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 116
SAFETY REF. NO. PART NAME & DESCRIPTION QTY. CS-CZ9SKE CS-CZ12SKE REMARK CHASSIS COMPLETE CWD50C1903 ← FAN MOTOR ARW7666ACCB ← CROSS-FLOW FAN COMPLETE CWH02C1159 ← BEARING ASSY CWH64K1010 ← SCREW - CROSS-FLOW FAN CWH551146 ← EVAPORATOR ACXB30C02040 ACXB30C02110 FLARE NUT (LIQUID) CWT251030 ←...
21.2 Outdoor Unit Note The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 118
CWH13C1253 ← REACTOR G0C193J00004 ← V-COIL COMPLETE (4-WAYS VALVE) ACXA43C00250 ← V-COIL COMPLETE (EXPANSION VALVE) CWA43C2603 ← PANASONIC BADGE CWE373439 ← NORDIC HEATPUMP BADGE CWE373985 ← HEATER (BASE PAN) CWA341072 ← (NOTE) All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).