Panasonic CS-CZ9SKE Service Manual page 76

Hide thumbs Also See for CS-CZ9SKE:
Table of Contents

Advertisement

17.5.2
H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit or outdoor unit PCBs mounted.
Indoor unit or outdoor unit PCBs defective.
Indoor-outdoor unit signal transmission error due to wrong wiring.
Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
76

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-cz12skeCu-cz12skeCu-cz9ske

Table of Contents