Voltage Regulator - Allen-Bradley 1407-CGCM User Manual

Combination generator control module
Table of Contents

Advertisement

2
1
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Bool
3
1
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Bool
4
1
Bool
Bool
Bool
Bool
Bool
Bool
Bool
Bool
0
Spare2
1
Spare3
2
EngineIdle
3
Spare4
4
PF_VAR_Select
5
PF_VAR_En
6
AVR_FCR_Select
7
FltReset
0
AutoSyncEn
1
CheckSyncEn
2
PermissiveSyncEn
3
Spare5
4
Spare6
5
Bus A_B_Select
6
DeadBusClosureEn
7
InitiateSync
0
Clear_kW_Hrs (Rev. 2. )
Set_kW_Hrs (Rev. 3. or later)
1
Clear_kVAR_Hrs (Rev. 2. )
Set_kVAR_Hrs (Rev. 3. or later)
2
Clear_kVA_Hrs (Rev. 2. )
Set_kVA_Hrs (Rev. 3. or later)
3
Spare7
4
Droop_CCC_Select
5
V_DroopEn
6
Spare8
7
SoftwareExcEn
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
CGCM Unit Software Interface
Engine Idle
Power Factor/VAR Select
Power Factor/VAR Enable
Automatic Voltage
Regulator/Field Current Regulator
Select
Fault Reset
Auto Synchronization Enable
Check Synchronization Enable
Permissive Synchronization
Enable
Bus A/B Select
Dead Bus Closure Enable
Initiate Synchronization
Set/Clear kW Hours
Set/Clear kVAR Hours
Set/Clear kVA Hours
Droop/Cross Current
Compensation Select
Voltage Droop Enable
Software Excitation Enable
-
-
0=False, 1=True
0=PF, 1=VAR
0=Disabled,
1=Enabled
0=AVR, 1=FCR
0=De-assert,
1=Assert
-
0=Disabled,
1=Enabled
0=Bus A, 1=Bus B
0=Disabled,
1=Enabled
0=Inactive, 1=Active
0=De-assert,
1=Assert
0=Droop, 1=CCC
0=Disabled,
1=Enabled
0=Disabled,
1=Enabled