CGCM Unit Configuration
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
• Generator capability curve
• Generator decrement curve
Consult with the generator manufacturer to be sure that you have the correct
data.
Verify and record system information and generator information required for
configuration of the CGCM unit. Typically this information can be obtained
from the generator nameplate, manufacturer's data sheets, and system electrical
drawings.
You need a suitable personal computer running RSLogix 5000 software. The
software is used to configure the CGCM unit for desired operation. RSLogix
5000 software contains a device profile that provides a user interface to the
CGCM unit configuration.
Refer to the CGCM Release Notes, publication 1407-RN001, for information
on compatible RSLogix 5000 software versions and ControlLogix controller
firmware revisions.
Follow these steps to create a new module in the ControlLogix controller with
RSLogix 5000 software.
You must be offline when you create a new module.
1. Under I/O Configuration, right-click 1756-CNB(R) and choose
New Module from the menu.
The Select Module Type dialog box appears. Add the CGCM unit as a
ControlNet module under the 1756-CNB(R) ControlNet Bridge module
in the controller.