FEEDER DOES NOT FEED
1.
No pellets in hopper.
2. Firebox draft may be too low for low draft pres-
sure switch in feeder circuit to operate. Check for
closed doors, loose or rnissing gasket on doors
or hopper lid, faulty pressure switch.
3.
Feed motor will not run until ESP
senses
165
deg. F. Maybe you did not put
enough pellets in the burn pot before lighting the
fire.
4.
Something is restricting flow in the hopper or
causing the slide plate to stick.
5.
Feed motor has failed.
PAR'I'IALLY BURNED PELLETS
1.
Feed rate too high.
FIRE HAS GONE OUT
1 .
No pellets in hopper.
2. Draft setting is too low.
3. Something is restricting fuel flow.
4.
Feed motor or draft motor has failed.
5.
Power failure or blown fuse.
SMOKE IS VISIBLE COMING OUT OF VENT
1
.
Air-fuel ratio is too rich.
A. Feed rate too high.
B. Draft too low caused by a gasket leak.
LOW HEAT OUTPUT
1 .
Feed rate too low
2. Draft too low because of gasket leak.
3.
Poor quality or damp pellets
4.
Combination of
I.
and 2.
3. Burn p i t or heat exchanger tubes may need to
be cleaned.
4.
Combination of all the above.
5. #6
status blink: A
6
blink control board status
indication is caused by poor or incomplete com-
bustion. The Advance Automatic Ignition circuit
board has the ability to track the combustion through
feed settings and ESP temperatures. When the
control board has calculated poor or incomplete
combustion it will shut down the unit as a safety
feature. (Poor or incomplete combustion is a
contributer of creasote which may cause a chim-
ney fire)
A
6
blink status may be caused by several things:
1. Blocked or partially blocked flue.
2. Blocked or partially blocked inlet air.
a. backdraft damper on the inlet pipe may be
stuck closed.
b. if outside air is installed the inlet cover may be
Cleaning Burn Pot
Whenever your stove is not burning, take the op-
portunity to scrape the burn pot to remove carbon
buildup. A vacuum cleaner is handy to remove the resi-
due. Be sure the stove is cold if you use a vacuum.
Carbon buildup can be scraped loose with the fire
burning using the special tool provided with your stove.
Scrape the floor and sides of the burn pot. The carbon
will be pushed out by the incoming fuel. Always wear
gloves to do this.
Removing Ashes
Turn the Temp Dial to number 1 approximately 30
minutes before removing ashes. This will result in a
cooler stove and ash pan.
Maximum Feed Adjuster settings are not needed
in most cases. Operating in the normal range
(#4)
is
recommended when maximum heat output is not re-
quired. The ESP probe prevents the stove from being
over-fired.
Keep the stove free of dust and dirt.
blocked.
3. The air chamber under the burnpot may be filled
with fines and small bits of ash.
4.
The holes in the burr~pot may be getting filled
Pellet fuels are put into 3 categories in terms of
with ash or carbon buildup.
ash content. Premium at
1%
or less, Standard at
3%
or
5.
Combustion blower fan blades may need
less and all others at 3% or more.
cleaned.
The Accentra is capable of burning all 3 categories
6.
Combustion intake assembly not properly
of pellets due to a patented feeder and burn pot system.
latched.
It should be noted, however, that higher ash con-
tent yill require more frequent ash removal .and may
7. No fuel in hopper.
SMOKE SMELL
provide less BTU's per pound. Normally, standard and
high ash pellets cost less than premium pellets and can
Seal the vent pipe joints and connection to stove be
effective when burned in the Accentram
with silicone.
The moisture content must not exceed 8%. Higher
moisture will rob BTU's and may not burn properly.