Notes on operation

4.3 Main and substitute telecontrol server

● For telecontrol connections:
Note
Wake-up with a mobile phone
 One of the texts listed above can be used in a wake-up SMS message.
 With a wake-up call, the station always connects to the main telecontrol server.
● For TeleService connections:
4.3
Main and substitute telecontrol server
Telecontrol server: Main and substitute server
If TCSB is installed as the main and substitute server, two parallel systems are installed by
TCSB and these are independent of each other. Both systems have their own database and
the complete communications functions of TCSB. The two TCSB systems do not monitor
each other.
36
– Text for the wake-up SMS message for establishing a connection to the telecontrol
server:
TELECONTROL
– Text for the wake-up SMS message for establishing a connection to the main
telecontrol server:
TELECONTROL MAIN
– Text for the wake-up SMS message for establishing a connection to the substitute
telecontrol server:
TELECONTROL BACKUP
The configuration of the telecontrol server for the CP 1242-7 is set in STEP 7 in
"Telecontrol interface > Operating mode > main or substitute telecontrol server".
– Text for the wake-up SMS message for establishing a connection to the first
configured TeleService server:
TELESERVICE
or
TELESERVICE 1
– Text for the wake-up SMS message for establishing a connection to the second
configured TeleService server:
TELESERVICE 2
For TeleService, no extra wake-up SMS needs to be sent since the connection
establishment is initiated by the engineering station.
The configuration of the TeleService server for the CP 1242-7 is set in STEP 7 in
"Telecontrol interface > TeleService settings.