Configuration
5.4 Configuring the telecontrol instructions
Field for monitoring times
In STEP 7, the corresponding data is located in the parameter areas "Acknowledgment
monitoring" and Operating mode".
Table 5- 13
IF_CONF_TC_Timeouts
Parameter
Id
Length
Mode
KeepAliveTimeout
SendTimeout
RedialTimeout
Field for the "Wake up right" parameter area
Table 5- 14
IF_CONF_WakeupList
Parameter
Id
Length
Mode
WakeupPhone [1...10]
Field for the "Preferred GSM networks" parameter area
Table 5- 15
IF_CONF_PrefProvider
Parameter
Id
Length
70
Data type
Initial value
UINT
12
UINT
UINT
-
-
UINT
UINT
Data type
Initial value
UINT
13
UINT
UINT
ARRAY [1...10]
of STRING [22]
Data type
Initial value
UINT
14
UINT
Description
ID of the parameter field
Length of the parameter field in bytes: 12
Validity (1: permanent, 2: temporary)
- Reserved - (cannot be set)
Acknowledgment monitoring time: Monitoring time for the
arrival of the TCP acknowledgment from the
communications partner after sending frames (seconds)
Only relevant for telecontrol connections
Dialing repetition delay: Basic value for the wait time until
the next attempt to establish a connection following an
unsuccessful connection establishment. After every 3
attempts, the basic value is doubled up to a maximum of
900 s. Range of values: 10 to 600 s. If a substitute
telecontrol server is configured, the CP attempts to
connect to it at the 4th dialin attempt. Example: Basic
value 20 results in the following dialing intervals: three
times 20 s, three times 40 s, three times 80 s etc. up to a
maximum of 900 s.
Not relevant for SMS connections
Description
ID of the parameter field
Length of the parameter field in bytes: 246
Validity (1: permanent, 2: temporary)
Phone number subscriber authorized to wake up
The asterisk (*) at the end of a call number is used a
placeholder for direct dialing numbers.
Description
ID of the parameter field
Length of the parameter field in bytes: 46
Operating Instructions, 09/2011, C79000-G8976-C247-02