Siemens N 562/11 Technical Product Information

Gamma instabus, switching actuator, main module 3x ac 230/400 v, 10 ax, c-load, load-check

Advertisement

Quick Links

N 562/11 Switching actuator, main module
3x AC 230/400 V, 10 AX, C-load, load-check
Product and functional description
The switching actuator main module N 562/11 is a DIN-
rail mounted device with N-system dimensions. It can
switch three groups of electrical consumers, independent
of each other, via its three relay contact outputs. The bus
is connected via a bus terminal block. The actuator elec-
tronics are supplied via the bus voltage.
Connection of switching actuator submodules
A switching actuator submodule N 562/21 or N 512/21
(see device B in figure 1) can be connected to the switch-
ing actuator main module N 562/11 (see device A in
figure 1) via the 6-pin interface with a special jumper. A
further switching actuator submodule can be connected
likewise to a previous switching actuator submodule. In
total up to 4 switching actuator submodules N 562/21 or
N 512/21 can be connected in series to a switching ac-
tuator main module N 562/11, so that a main module, if
need be, can be extended simply from a 3-fold to a 6-, 9-,
12- or 15-fold switching actuator and thus be matched
flexibly to the size and number of loads to be switched.
LED display
Five green light emitting diodes (LED) on the top of the
main module (see figure 2, A5) indicate which module is
selected (LED = ON). A module can be selected by tap-
ping the pushbutton "Direct mode" (see figure 2, A6)
once or several times until the LED of the desired module
A to E illuminates. If any of the green LED A to E is flash-
ing a fault was detected at this module. For example, this
is the case if more modules are configured than are actu-
ally connected or if the configured module type does not
Siemens AG
Industry Sector, Building Technologies
Low Voltage Distribution
P.O. Box 100953, D-93009 Regensburg
correspond with the module type actually connected or if
a module is detected as faulty.
Bus mode / Direct mode
The Direct mode pushbutton (see figure 2, A6) with an
integrated yellow LED may be used to toggle between
Bus mode and Direct mode. If this pushbutton is pressed
briefly, the associated green LED indicates for 30 seconds
which of the modules A to E (see figure 2, A5) was se-
lected last and the switching state of the corresponding
outputs is indicated by the red LED integrated in buttons
1 to 3 (see figure 2, A9; relay contact closed: LED = ON,
contact open: LED = OFF).
However, if the button to switch on Direct mode is held
down for at least 3 seconds, then the yellow LED to indi-
cate Direct mode turns on permanently. In Direct mode,
each output of the currently selected module can be
switched via the allocated pushbutton on the top of the
main module through a toggling function: a first press on
the pushbutton switches the output on if it is switched
off, a second press switches it off again. The switching
state of the output is indicated by the red LED incorpo-
rated in the pushbutton. (Note: Pushbuttons 4 to 6 and
the incorporated LED are not used in the N 562/11.) To
change the switching state of the outputs of another
module, this module must be selected first. To do this,
you must briefly press the Direct mode pushbutton sev-
eral times until the LED of the desired module A to E
illuminates. Modules that are connected but not yet set
up as connected cannot be selected.
A parameter determines whether Direct mode can be
switched on permanently or for a limited period. The
factory default setting limits the Direct mode period to
15 minutes. Each time the pushbutton is pressed the
timer is reset to 15 minutes. After the period has elapsed
without a further key press, Direct mode is switched off
automatically and Bus mode is re-enabled accordingly (if
communication via the bus is possible). Alternatively,
Direct mode can be left at any time by pressing the Direct
mode pushbutton for at least 3 seconds. Then the yellow
LED for indicating Direct mode turns off and the actuator
operates in Bus mode. In Bus mode, pressing the
pushbutton for direct switching of an output off or on
does not work. If Direct mode is active, switching and
scene recall commands received via the bus are buffered
and automatically executed after switching back to Bus
mode.
Behavior in case of mains failure / recovery
Because the actuator electronics are fed from the bus, a
mains failure then leads solely to a failure of the actuator
function if the bus voltage also fails as the result of a
mains failure. However, it can be set for each actuator
output individually which switching state it is to assume
on a bus voltage failure and after the bus voltage recov-
ery: as before bus voltage failure, ON or OFF.
N 562/11, 6 pages
© Siemens AG 2009
Subject to change without further notice
GAMMA instabus
Technical product information
December 2009
5WG1 562-1AB11
Technical manual
Update: http://www.siemens.com/gamma
2.4.3.4/1

Advertisement

loading

Summary of Contents for Siemens N 562/11

  • Page 1 LED incorpo- rated in the pushbutton. (Note: Pushbuttons 4 to 6 and the incorporated LED are not used in the N 562/11.) To change the switching state of the outputs of another module, this module must be selected first.
  • Page 2: Application Program

    Software (ETS) is required as version 3.0 f or higher. • The device can be used for permanent installation in Note: If the N 562/11 application program is "unloaded" dry interior rooms and for insertion in distribution with the ETS, then you will no longer be able to activate boards or miniature housings.
  • Page 3: Technical Data

    • Power dissipation: if all outputs = OFF: 0.2 W, tor sleeve at max. load and all outputs = ON: approx. 3.5 W. • Each L-conductor connection to the N 562/11 must be fused, depending on the type of load, with a circuit- Outputs breaker of characteristic B or C for a max.
  • Page 4: Installation And Wiring

    GAMMA instabus Technical product information December 2009 N 562/11 Switching actuator, main module 5WG1 562-1AB11 3x AC 230/400 V, 10 AX, C-load, load-check Location and function of the display and operating elements Figure 4. Dismounting the device Connecting / disconnecting the bus cable: see figure 5 D2.3...
  • Page 5: General Notes

    • The operating instructions must be handed over to the client. • A faulty device shall be sent with a Return Good Note for Service provided by the appropriate Siemens sales office to the following address: SIEMENS AG, Siemensstr. 10, D-93055 Regensburg •...
  • Page 6 GAMMA instabus Technical product information December 2009 N 562/11 Switching actuator, main module 5WG1 562-1AB11 3x AC 230/400 V, 10 AX, C-load, load-check Space for notes Technical manual N 562/11, 6 pages Siemens AG Industry Sector, Building Technologies Update: http://www.siemens.com/gamma ©...