Protection functions
Table 30. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on
stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one phase with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
PHLPTOC
PHHPTOC
and
PHIPTOC
PHIPTOC:
I
= 2 x set Start
Fault
value
I
= 10 x set Start
Fault
value
PHHPTOC:
I
= 2 x set Start
Fault
value
PHLPTOC:
I
= 2 x set Start
Fault
value
Value
At the frequency f = f
n
±1.5% of the set value or ±0.002 x I
±1.5% of set value or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0% of the set value
(at currents in the range of 10...40 x I
Typical: 17 ms (±5 ms)
Typical: 10 ms (±5 ms)
Typical: 19 ms (±5 ms)
Typical: 23 ms (±15 ms)
< 45 ms
Typical 0.96
< 30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50 dB at f = n x f
n
...
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1MRS756978 D
Issued: 2011-05-18
n
n
)
n
)
n
3)
, where n = 2, 3, 4, 5,
29