ABB Relion 630 Series RET630 Product Manual page 42

Transformer protection and control
Table of Contents

Advertisement

Transformer Protection and Control
RET630
Product version: 1.1
Table 49. Transformer differential protection for two-winding transformers (TR2PTDF)
main settings
Parameter
Restraint mode
High operate value
Low operate value
Slope section 2
End section 2
Start value 2.H
Start value 5.H
Winding 1 type
Winding 2 type
Zro A elimination
Clock number
42
Function
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
TR2PTDF
Value (Range)
2.h & 5.h & wav
Waveform
2.h & waveform
5.h & waveform
500...3000 %
5...50 %
10...50 %
100...500 %
7...20 %
10...50 %
Y
YN
D
Z
ZN
Y
YN
D
Z
ZN
Not eliminated
Winding 1
Winding 2
Winding 1 and 2
Clk Num 0
Clk Num 1
Clk Num 2
Clk Num 4
Clk Num 5
Clk Num 6
Clk Num 7
Clk Num 8
Clk Num 10
Clk Num 11
1MRS756978 D